REV
.03-(16.03.2015)
3 - Connect the pressure gauge connect on tube to the pos t ve
port of the test ng n pple and check the gas supply pressure.
4 - Connect the pressure gauge connect on tube to the burner
pressure tap and check the burner supply pressure. Burner
pressure must be adjust accord ng to the table. Check that
the CO values are w th n the values nd cated n the table.
2
Correct the value by turn ng the adjustment screw (C) n
clockw se d rect on to decrease the value and n an ant -
clockw se d rect on n order to ncrease the value.
4.3.4
M n mum output adjustment
2 - Connect the pressure gauge connect on tube to the burner
pressure tap and check the burner supply pressure. Burner
pressure must be adjust accord ng to the table. Check that
the CO values are w th n the values nd cated n the table.
2
Correct the value by turn ng the adjustment screw (A) n
clockw se d rect on to ncrease the value and n an ant -
clockw se d rect on n order to decrease the value.
3 - Check the
values at the m n mum and max mum output.
CO
2
Make the requ red adjustments f necessary.
values
CO
2
have to be adjusted w th extreme care respect ng the values
nd cated n the table. When the adjustments have done,
close sampl ng test po nt n the flue adapter w th the cap.
Instruct ons for the nstaller
17
1 - For operat ng n the m n. output, press at least 3 seconds to
heat ng mode when the bo ler n mode.Controller funct on stop
w ll appear on the screen.Than press nformat on button, t w ll
nd cate the modulat on rate (%) on the screen. Adjust the rate to
0% for m n. output sett ng w th us ng of nav gat on button. Then
press OK . Thus, bo ler w ll operate n m n mum power.
0 %
...... mbar
...... mbar
Burner(outlet) pressure tap
D
Max mum output
adjustment screw
C
1
Remove the screw
3
Fasten the screw
Connect the gauge
...... mbar
2
...... mbar
2
Inlet pressure tap
B
M n mum output adjustment screw
A
...... mbar
...... mbar
Burner(outlet) pressure tap
D