20
(6)
Safety instructions for transportation and storage
:
- Please use the flammable gas detector to check before unload and open the container. No fire source
and smoking.
- According to the local rules and laws.
9.
Installation of Hydraulic Unit
9.1.
Available External Static Pressure of Outlet
Note :
See the curve above for the maximum external static pressure. The water pump is of variable frequency.
And during operation, the water pump will adjust its output based on the actual load.
9.2.
Water volume and expansion vessel pressure
Note :
(a) The expansion vessel is 2 liter and 1.5bar pre-pressurized for 4/6/8kW unit; 3 liter and 1.5bar per-
(b) pressurized for 10/12/14/16kW unit ;
(c) Total water volume of 44 liter is default for 4/6/8kW unit and 66 liter for 10/12/14/16kW unit; if total water is
changed because of installation condition, the pre-pressure should be adjusted to secure proper operation.
If the unit is located at the highest position, adjustment is not required;
(d) Minimum total water volume is 20 liter;
(e) To adjust pre-pressure, use nitrogen gas by certificated installer.