
Part 14 - Troubleshooting
Code
Possible cause
Solution
01
Supply and return switched at installation
Check CH connections
02
CH set point adjusted too low
Check parameter 0
03
Max CH modulation set too low
Check parameter 1
04
Max modulation time too long
Check parameter 2
05
Pump speed too low
Check speed in diagnose menu (24) and check parameter 4 and 5
06
Boiler is not able to distribute generated heat
Check installation for sufficient flow
07
Outdoor sensor used
Check heating curve parameters 7,8,9,10
08
Air in CH circuit
Vent the CH circuit
09
Calibration not completed correctly
Perform calibration
10
Distance / gap electrode not correct
Check electrode gap and distance to burner
11
Ignition electrode damaged
Replace ignition electrode
12
Room thermostat connected incorrectly
Check cabling and connection to room thermostat
13
Opentherm thermostat connected
Set point thermostat (CH temperature) is lower than actual CH temperature. Check item 4 and 5 in
diagnose menu.
14
Thermostat does not switch off
Replace thermostat
15
Opentherm thermostat connected
Set point thermostat (CH temperature) is higher than actual CH temperature. Check item 4 and 5 in
diagnose menu.
16
Main heat exchanger cluttered
Clean heat exchanger
17
CH pressure too low
Re-fill installation
18
3-way valve cluttered
Check and clean 3-way valve when required
19
3-way valve does not change position
Check valve actuator and cables. Replace when required
20
Readout flow sensor incorrect
Check flow sensor in diagnose menu (07)
21
Solar tank used to feed boiler
Check availability and setting mixing valve
22
Setting DHW set point too high
Check parameter 12
23
DHW sensor damaged
Check DHW temperature via diagnose menu (8) and replace sensor when required
24
Too high DHW flow over boiler
Check use of correct (and undamaged) flow restrictor
25
Plate heat exchanger cluttered at CH side
Check plate heat exchanger
26
Gas valve closed
Open gas valve
27
No gas supply
Gas pressure regulator stuck or broken, gas valve closed, check grid pressure
28
Ignition cable broken or not connected
Check ignition cable
29
Ignition cable cap damaged
Check for cracks. Replace when required
30
Ignition transformer damaged
Check if the unit sparks and check the distance and gap of the electrode. If all OK replace burner
controller.
31
Water in ionisation circuit
Check for water (humidity), dry and check operation. Replace when required
32
Dirt in gas valve
Check if valve fully closes when power is unplugged
33
Flue gas sensor damaged
Exchange sensor and check parameter 14
34
Wrong setting of temperature limit configuration
Check parameter 14
35
Maximum power too high
Check boiler power and adjust parameter 1 when required
39
Pump does not run is stuck
Replace pump or try to turn pump shaft.
40
Refill valve is open
Close refill valve
41
Cable damaged
Check cables for damage and friction free routing
42
Sensors switched
Check sensor positions and connections
43
Supple sensor broken
Check sensor in diagnose menu (4) and replace when required
44
Siphon cluttered (condensate cup)
Clean siphon
45
Too high circulation losses or demand
Boiler is not able to heat tank to a temperature above 70C within 3 hours. Check recirculation losses and
heat exchanger tank
46
Gas valve cables damaged
Check cables and replace when required.
47
Gas valve broken
Check gas valve and replace when required.
48
Leakage in CH circuit
Exchange leaking installation part s and refill
49
CH pressure too high
Decrease pressure using the drain valve
50
Expansion vessel broken
Check expansion vessel
51
No temperature rise detected within 1 minute
Check position of supply sensor and flue gas sensor. Check sensor readings via diagnose menu and
after ignition or sensor broken
replace sensor(s) when required
52
No outdoor sensor connected
Check parameter 7
53
Outdoor sensor broken
Check reading via diagnose menu (11) and replace sensor when required
54
CH return sensor broken
Check reading via diagnose menu (6) and replace sensor when required
55
Supply voltage too low
Check supply voltage in standby and operation
56
Supply cable damaged
Replace supply cable
57
Fan not connected
Check fan connection to burner control
58
Too much dust/dirt in fan
Check and clean fan
59
Fan broken
Replace fan
60
Water on fan connection
Check fan and connection and make dry when required
61
CH pressure sensor broken
Check reading via diagnose menu (3) and replace when required
62
DHW sensor broken
Check reading via diagnose menu (7) and replace when required
63
Incorrect connection to earth
Check earth in supply cable and supply cable connections
64
No tank nor tank sensor present
Check parameter 11
65
Tank sensor broken
Check reading via diagnose menu (12) and replace when required
66
No code key or faulty connection
Install code key and or check connections
67
Code key broken
Replace code key
68
Boiler cannot distribute heat due to high system
Perform calibration with DHW demand to be able to distribute generated heat
temperatures
69
Calibration not successfully completed
Perform calibration and check diagnose menu (32)
70
Blocked flue
Check flue pipe for blockages
71
Change in flue system after calibration
Perform calibration
72
Magnetite filter cluttered
Check and clean filter
73
CH return restrainer cluttered
Clean hydro block CH return connection
74
Resistance in gas supply pipe too high
Check pressure drop over gas supply system too boiler. Contact grid owner when required
75
CH pressure sensor broken
Replace sensor. When required sensor can be deactivated temporarily. Parameter 20.
76
Gas / air mixture incorrect
Check fan air intake for cracks and secure placement of the air intake sticker.
77
Burner control broken
Replace
78
Fan calibration time is running
Fan calibration has not completed during calibration process. Wait 10 minutes to finalize calibration.
Table 14.3 Possible causes and solutions
76