Part 10 - Lighting the appliance / First start-up
Parameter
Description
Unit
Default
Min.
Max.
Note
no.
Imperial
(SI)
0
Maximum CH
°C (°F)
80 (176)
20 (68)
85 (185)
temperature
setting
1
Maximum CH
%
100
0
100
power
2
Maximum time for
Minutes
10
0
60
modulation
to full power
3
Pump overrun time
Minutes
1
0,5
C (continues)
Time max. 30 min.
CH
C=Pump continuously
4
Maximum flow
%
100
50
100
pump for CH
operation
5
Minimum flow
%
50
40
100
pump for CH
operation
6
dT Supply/Return
K/°F
15/28
5/9
30/54
K=displayed on old boilers
AQM17..
°F=shown on new boilers serial
AQM20..and later
CH operation
7
Outside sensor
0
0
1
0=no outside sensor
present
1=outside sensor
present / weather dependent
control activated
8
K factor for
4
0.5
6
weather-dependent
control
9
K factor for
2
0.5
6
weather-dependent
control night mode
10
Offset outside
K / °F
0 / 0
-15 / -27
+15 / 27
K=displayed on old boilers AQM17..
°F=shown on new boilers serial
AQM20..and later
sensor set point
11
Tap water
0/1
0
2
0= Hxx default (No DHW)
configuration
1= Cxx default (Combi)
2= Hxx storage tank operation
12
Required tap water
°C (°F)
61 (142)
40 (101)
70 (158)
temperature
14
Flue gas sensor
2
0
2
0= High limit switch
type
1=NTC
2=High limit switch
and NTC
15*
Gas type
1
1
2
1 = Natural gas G20
2 = LPG*.
16
Option print
0
0
99
configuration
17
Anti fast-cycle time
Minutes
2,5
0
10
18
Maximum power
%
100
0
100
DHW
19
0
0
1
Not used.
Do not change.
20
Pressure sensor
0
0
1
0 = activated
de-activated
1 = deactivated
21
Reset to default
0
0
255
111 = reset to factory defaults
values
(requires manual calibration)
22**
°F & PSI Setting
1
1
2
1=LCD screen displays PSI
and °F
Table
10.1Setting
parameters
•
*FOR PROPANE usage. On
C100, C140, H100 and H140 units, the
does not require a gas
pipe changed, only a setting change on 15 from 1 to 2. When using propane on a H200 or C200 the Gas
pipe in the boiler MUST BE CHANGED. It is a separate part NOT included in the box and needs to be
ordered from your supplier. Part number
202-1331
•
**All boilers with serial numbers AQM19…., AQM20…, and higher will display PSI and °F by default and do
not have capability to switch to °C and Bar. The °F and PSI boilers will have an LCD screen sticker on the
back that show CP37.03. Old ones with °C and Bar will show CP37.02