Installation Manual, Maintenance and Operation
Pressure Regulating Valve – Model Horus
MI-18
Elaborate
Verified / Approved
CSQ
Date
Review
Page
J.Junior
Celso Nieto
JM
25/11/16 04
17 de 32
4.6.4 LIST OF RECOMMENDED TOOLS
To perform the adjustment set-point commissioning and start-up of regulatory URANO GASCAT the
model is required only the use of a combination wrench 7/8 "to adjust the regulation of pilots springs.
The valves are URANO model fornecdias with connectors for tubbing DN ½ "in the sensor plugs, so we still
recommend the use of combination wrenches 19 mm and 13/16" for fixing the sensor taken the process line.
ND
1
2
1”,2”,3”,4”,6”, 8” and 10”
19 mm, 7/8” e 13/16”
1”
5.0 TROUBLE SHOOTING
This section of the manual aims to show potential field problems and their causes.
The problems listed in this section may be from different situations, but most of them is related to the gas
conditions (impurities), natural wear and failures during operation of the equipment.
It is important to keep in mind that the operation and maintenance of GASCAT equipment must be only carried out
by highly qualified and trained personnel, preferably by staff trained by GASCAT instructors.
For training and qualification of operators and technicians contact the GASCAT through the contacts below to
check availability.
E-mail:
HORUS
PROBLEM
PROBABLE CAUSE
CORRECTIVE ACTION
Malfunction, outlet pressure oscillation
Low flow (less than 5% of the
maximum flow).
Check the operating conditions
and restore the flow conditions for
the standards to which the
equipment has been designed.
Making poorly localized impulse.
Adjust the position of the pulse
taken as reported in this manual,
or contact the GASCAT for
analysis of engineering.
Response speed of the regulator
incompatible with the system.
Adjust the unloading valve
(needle).
1
2