Installation
5.3 Installing the Pedestal Base
Page 38
MDE-5411A ForeHB Islander Prime Installation Manual · October 2018
When mounting Islander Prime, a minimum clearance of 18-inches (0.5-m) between the unit
and any of the pumps or the dispensers must be maintained. This clearance ensures that a safe
amount of room is available for the wiring and maintenance of the system, and that the system
complies with fire codes.
Islander Prime is designed and approved for installation and use at a convenient location at or
near the fuel Island in the appropriate hazardous (classified) location:
• Where hazardous location is classified as Class 1, Division 2, and it does not extend higher
than 18-inches (0.5-m) from surface.
• A minimum safety separation of 18 inches (0.5-m) from any nearest pump or dispenser.
5.3 Installing the Pedestal Base
The Islander Prime pedestal is mounted in the homebase station on a base plate that is fastened
to the homebase station concrete floor (see
). The upper side of the base
plate includes four holding screws set in the homebase station concrete floor.
Figure 18: Base Plate Dimensions
Table 6:
Measurement
Dimension
Anchor Bolt Holes
10
.
5
0
mm x 4 |
0.
41 in
.
x 4
Base Plate Central Opening
200 x 200 mm | 7.87 x 7.87 inch
Islander Prime Base Plate Dimensions