background image

engine will shut off.

 

Release the TEST button. After the engine stops, press the 
RESET button or remove battery power. Restart the engine 
and it will return to the original speed setting. The overspeed 
function is now set to approximately 10% above the request-
ed speed.

 

 

If a different value of overspeed setting is required, raise the 
engine speed to the desired overspeed value, i.e. 115%. Ro-
tate the OVERSPEED adjustment CCW until the red OVER-
SPEED LED lights and the relay energizes

.

 

  

WARNING

 

 

Always use the relay contacts provided to shut down the 

system by a means other than the governor or actuator. It 

is recom-mended that an overspeed protection sys-tem be 

routinely tested and verified during the scheduled service 

of equipment.

 

 
 

Governor Speed Setting

 

 

The governed speed set point is increased by a CW rotation 
of  the  SPEED  adjustment  control.  Remote  speed  adjust-
ment can be obtained with an optional 5K Speed Trim Con-
trol. (See Diagram 1.)

 

 

Governor Performance

 

 

Once the engine  is at operating speed  and at no  load, the 
following governor performance adjustment can be made.

 

 

A.

 

Rotate  the  GAIN  adjustment  CW  until  instability  devel-
ops. Gradually move the adjustment CCW until stability 
returns. Move the adjustment one division further CCW 
to insure stable performance. 

 

B.

 

Rotate the STABILITY adjustment clockwise until insta-
bility  develops.  Gradually  move  the  adjustment  coun-
terclockwise until stability returns. Move the adjustment 
one division further to insure stable performance (270° 
pot). 

 

C.

 

GAIN  and  STABILITY  adjustments  may  require  minor 
changes  after  engine  load  is  applied.  Normally,  ad-
justments made at no load achieve satisfactory  perfor-
mance.  A  strip  chart  recorder  can  be  used  to  further 
optimize the adjustments. 

 

If  instability  cannot  be  corrected  or  further  performance 
improvements  are  required,  refer  below  to  the  SYSTEM 
TROUBLESHOOTING section.

 

 

Starting Fuel Adjustment

 

 

The engine’s exhaust smoke at start-up can be minimized 
by completing the following adjustments:

 

 

A.

 

Place the engine in idle by connecting Terminals M & G. 

 
B.

 

Adjust the IDLE speed for as low a speed setting as the 
application allows. 

 
C.

 

Adjust the STARTING FUEL CCW until the engine speed 

 

  

begins to fall. Increase the STARTING FUEL slightly so 
that the idle speed is returned to the desired level.

 

 

D.  Stop the engine.

 

 

One of two methods of operation for the ESD5550/5570 
may now selected. (See Table 2.)

 

 

Table 2 Starting Method

 

 

Method 1

 

 

Method 2

 

 

Start the engine and accelerate

   

Start  the  engine  and  control

 

 

directly to the operating speed

 

 

at an idle speed for a period of

 

 

(Gen Sets, etc.).

 

 

time prior to accelerating to the

 

 

 

 

operating speed.  This method

 

 

 

 

separates the starting process

 

 

 

 

so that each may be optimized

 

 

 

 

for the lowest smoke emissions.

 

 

 

 

 

 

Remove the connection between

 

 

Replace  the  connection  be-

 

 

Terminals M & G. Start the en-

 

OR

 

tween Terminals M & G with a

 

 

gine  and  adjust  the  SPEED

 

switch, usually an oil pressure

 

 

RAMPING for the least smoke

 

 

switch.  Start the engine.  If the

 

 

on acceleration from idle to rated

 

 

starting  smoke  is  excessive,

 

 

speed.  If the starting smoke is

 

 

the STARTING FUEL may need

 

 

excessive, the STARTING FUEL

 

 

to be adjusted slightly CCW.  If

 

 

may need to be adjusted slightly

 

 

the starting time is too long, the

 

 

CCW. If the starting time is too

 

 

STARTING FUEL may need to

 

 

long, the STARTING FUEL may

 

 

be adjusted slightly CW.

 

 

need to be adjusted slightly CW.

 

 

 

 

 

 

When the switch opens, adjust

 

 

 

 

the SPEED RAMPING for the

 

 

 

 

least  amount  of  smoke  when

 

 

 

 

accelerating from idle speed to

 

 

 

 

rated speed.

 

 

 

 

 

 

 

Idle Speed Setting

 

 

If  the  IDLE  speed  setting  was  not  adjusted  as  detailed  in 

‘Starting  Fuel  Adjustment’  section,  then  place  the  optional 
external selector switch in the IDLE position. A CW adjust-
ment  to  the  IDLE  adjustment  control  will  increase  the  idle 
speed set point. When the engine is at idle speed, the speed 
control unit applies droop to the governor system to insure 
stable operation.

 

 

Speed Droop Operation

 

 

Droop  is  typically  used  for  the  paralleling  of  engine  driven 
generators.

 

 

Place the optional external selector switch in the DROOP po-
sition. DROOP is increased by CW rotation of the DROOP 
adjustment  control.  When  in  droop  operation,  the  engine 
speed will decrease as engine load increases. The percent-
age of droop is based on the actuator current change from 
engine no load to full load. A wide range droop is available 
with  the  internal  control.  Droop  level  requirements  above 
10% are unusual.

 

 

If  droop  levels  experienced  are  higher  or  lower  then  these 
required, contact GAC for assistance.

 

 

After  the  droop  level  has  been  adjusted,  the  rated  engine 
speed  setting  may  need  to  be  reset.  Check  the  engines 
speed and adjust that speed setting accordingly.

 

 

 
 

 

2

 

Summary of Contents for ESD5550 Series

Page 1: ... satisfactory air gap The magnetic speed sensor voltage should be at least 1 VAC RMS during cranking Before Starting Engine Before starting the engine check and or adjust the POTs switches to the following settings See Table 1 for the fac tory presets Start Engine The speed control unit governed speed setting is factory set at approximately engine idle speed 1000 Hz speed sen sor signal Crank the ...

Page 2: ...L slightly so that the idle speed is returned to the desired level D Stop the engine One of two methods of operation for the ESD5550 5570 may now selected See Table 2 Table 2 Starting Method Method 1 Method 2 Start the engine and accelerate Start the engine and control directly to the operating speed at an idle speed for a period of Gen Sets etc time prior to accelerating to the operating speed Th...

Page 3: ...e Refer to Table 3 If the exact range cannot be found select the next higher range poten tiometer An additional fixed resistor may be placed across the potentiometer to obtain the exact desired range Con nect the speed range potentiometer as shown in Diagram 1 To maintain engine stability at the minimum speed setting a small amount of droop can be added turn the DROOP adjustment CW At the maximum ...

Page 4: ... from mod erate external interfering sources Although it is difficult to predict levels of interference applications that include mag netos solid sate ignition systems radio transmitters voltage regulators or battery chargers should be considered suspect as possible interfering sources If it is suspected that external fields either those that are radiated or conducted are or will affect the govern...

Page 5: ... continuous Speed Drift with Temperature 1 Maximum Idle Adjust CW 60 of set speed Idle Adjust CCW Less than 1200 Hz Crank Termination Adjustment Range 300 2200 Hz Droop Range 1 5 regulation Droop Adj Max K L Jumpered 400 Hz 75 Hz per 1 0 A change Droop Adj Min K L Jumpered 15 Hz 6 Hz per 1 0 A change Speed Trim Range 200 Hz Remote Variable Speed Range 500 7 5 Hz or any part thereof Speed Switch Ad...

Page 6: ...OP COMPENSATION ENGINE SPEED CONTROL JUMPER COMPONENT WHEN INSTALLING OR SERVICING REFER TO PRODUCT PUBLICATION PICK UP IDLE 10V ACTUATOR BATTERY AUX OUTPUT A B C D E F G H J K L M N P OPTIONAL ACTUATOR CABLE SHIELDING TO MEET CE DIRECTIVE ACTUATOR MAGNETIC CW PICK UP _ SPEED TRIM CONTROL 5K S1 BATTERY FUSE 15A MAX ACCESSORY POWER SUPPLY ACCESSORY INPUT ADD JUMPER FOR 12V BATTERY OR ACTUATOR CURRE...

Page 7: ...ROOP COMPONENT WHEN INSTALLING OR SERVICING REFER TO PRODUCT PUBLICATION PICK UP IDLE 10V ACTUATOR BATTERY AUX OUTPUT A B C D E F G H J K L M N P DEAD TIME COMPENSATION JUMPER OPTIONAL ACTUATOR CABLE SHIELDING TO MEET CE DIRECTIVE ACTUATOR MAGNETIC CW PICK UP _ SPEED TRIM CONTROL 5K BATTERY FUSE 15A MAX ACCESSORY POWER SUPPLY ACCESSORY INPUT ADD JUMPER FOR 12V BATTERY OR ACTUATOR CURRENTS ABOVE 5A...

Reviews: