9
WARNING: THIS HEAT ALARM MUST BE INSTALLED BY
QUALIFIED (LICENSED) ELECTRICIANS ONLY.
Wiring Requirements
• This heat alarm should be installed with an AS/NZS Wiring Rules
approved junction box. All connections must be installed by
a qualified electrician and be in accordance with the relevant
requirements of the SAA Wiring Rules AS 3000 Standards.
• The appropriate power source is 240V AC 50Hz continuous single
phase sine wave current supplied from a non-switchable circuit
which is not protected by a RCD.
• Heat alarms are not to be used with detector guards unless the
combination (alarm and guard) has been evaluated and found
suitable for that purpose.
•
WARNING:
This alarm cannot be operated from power derived
from a square wave or modified square wave inverter. These type
of inverters are sometimes used to supply power to the structure in
off grid installations, such as solar or wind derived power sources.
These power sources produce high peak voltages that will damage
the alarm.
Wiring instructions for AC harness
!
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT
BEFORE WIRING THE ALARM.
• For alarms that are used as single station,
DO NOT CONNECT
THE RED WIRE TO ANYTHING
. Leave the red wire insulating cap
in place to make certain that the red wire cannot contact any metal
parts or the electrical box.
• When alarms are interconnected, all interconnected units must be
powered from a single circuit.
• A maximum of 18
Garland OnGard
AUS safety devices may be
interconnected in a multiple station arrangement. The interconnect
system should not exceed the interconnect limit of 12 smoke alarms
and/or 18 alarms total (smoke, heat detector, etc.).