Installation
RTCSmp Built-In Temperature Controlled Hold-Line
10
Part # 4532288 Rev 3 (6/11/14)
When installing the built-in unit, ensure the intake air and exhaust air are conducted separately. The in-
take air and exhaust air must not mix. To avoid build-up of hot exhaust air inside the cabinet, draw the
exhaust air out of the cabinet. Build up of hot exhaust air will cause the induction unit to reduce power
or to switch-off. The air intake temperature must not exceed 104
F (40
C).
We recommend drawing fresh intake air through an air intake vent with a removable air intake filter.
It is highly recommended that an exhaust fan be installed into the cabinet at an appropriate location.
This will force hot air out the cabinet and away from the induction unit. Consult an electrical or
installation expert for the most appropriate location to install a cabinet exhaust fan.
4.3
Electrical Compartment Protection
To protect the equipment, isolate the unit and the wires in a separate electrical compartment inside the cabinet.
The illustrations below show two installation versions.
Figure (
A
) The unit is installed in one compartment and the wires are exposed.
Figure (
B)
The interior space of the cabinet is divided and the unit and the wires are protected inside
separate compartments. Extra storage space is also created next to the electrical compartments.
(
C
)
IMPORTANT
Fresh air intake through the fan. It is recommended to isolate the
fresh air intake from the exhaust air via an air intake duct and filter the intake air
with a removable air filter. (see example on right)
(
D
) Hot air exhaust from the induction unit.
(
E
)
IMPORTANT
Air exhaust opening installed on the cabinet. It is highly
recommended to install a fan or fans on the cabinet to pull the hot exhaust air
away from the electronic equipment. Buildup of hot exhaust air will cause the
induction unit to reduce power or to switch-off. The air intake temperature must
not exceed 40
C / 104
F.
(
F
)
IMPORTANT
Minimum clearance below the counter-surface for the unit:
(height x width x depth) 160x 780 x 380mm / 6.3”x 30.71”x 14.96”
(
G
) Cables for the operation units.
(
H
)
IMPORTANT
Fresh air supply through an air intake duct. Avoid drawing the hot exhaust air back into
the unit.
(
I
) When there is no direct path for the air duct to pass through, create an opening on an inner wall or shelf.
D
G
H
C
E
F
H
Figure
B
Figure
A
I
D
G
H
C
E
F
H
Air Intake Filter
Filter Holder
Filter Holder