13-17-609 Page 26
3-3
Operation with incorrect motor rotation can damage equipment and cause oil
eruption from the compressor inlet. When checking motor rotation, induce
minimum rotation (less than one revolution if possible). Never allow motor to
reach full speed.
The compressor unit’s direction of rotation must be checked every time the
compressor is reconnected to the power supply.
8.
System Pressure
- Set the controls to the desired load pressure. DO NOT EXCEED THE
MAXIMUM OPERATING PRESSURE ON THE COMPRESSOR NAMEPLATE.
Quick Start Guide
Operation of the AirSmart controller is easy. Simply select a Target Pressure and then press the Run
button to start the compressor, no other settings are required. The Target Pressure comes
preset to 100 PSI from the factory. The Unload Pressure is preset to 110 PSI. If a different pressure
setting is desired, the following steps can be used as a guide.
·
Setting the Target Pressure
The Target Pressure setting is used to set the operating point of the compressor. To make any
adjustments in the operation of the compressor, the machine must be stopped and in the Ready
mode. Stop the compressor by pressing the Stop/Reset
button. The front panel display
should read
“READY” on line 3.
Next, press the Enter
button to access the Adjustment Menu tree
Since the Target Pressure setting is under the Operation Adjustment menu, press Enter
again to access that sub-menu
0 PSI 75°F
10 HRS AUTOMATIC
READY
NO SERVICE ADVISORY
ADJUSTMENT MENU
OPERATION ADJUSTMENT
(SELECT SUB MENU)
OPERATION ADJUSTMENT
LANGUAGE-LANGUAGE
ENGLISH (US)
(SELECT PARAMETER)