13-18-606 Page 57
Operation of the unit with improper relief valve setting can result in severe
personal injury or machine damage. Ensure properly set valves are installed
and maintained.
Pressure Relief Valve Check During Operation –
The pressure relief valve has no user-serviceable or
repairable components. However, it should be tested for proper operation at least once every year. To
test the pressure relief valve:
•
Raise the system operating pressure to its normal level.
•
Turn the top cap on valve 1-2 turns counter-clockwise to open valve and let it vent for a few seconds.
•
Close the valve by firmly turning top cap clockwise. Make sure that cap is firmly tightened to avoid
damage by vibrations.