Leak detector Vakumatik IVF R34
5.3.
Other suitable tanks
-
Double walled tanks / containers
of a cylindrical, rectangular or spherical construction
made from metallic or non-metallic material having a general building authority certification
or at least with a statement by an authorized test department for leak detection systems,
indicating that the interstitial spaces are suitable when used in connection with the leak
detector and its switching values (see 4.1). The suction line of the leak detector has to be
installed down to the bottom of the interstitial space.
-
Single walled tanks / containers
of a cylindrical,
rectangular or spherical construction
made from metallic or non-metallic material with an approved leak protection lining having a
general building authority certification or at least with a statement by an authorized test
department for leak detection systems, indicating that the interstitial spaces are suitable
when used in connection with the leak detector and its switing values (see 4.1). The suction
line of the leak detector has to be installed down to the bottom of the interstitial space.
5.4.
Stored liquids that can be monitored via the leak detector:
-
Only liquids hazardous to water with a flash point >55°C (formerly AIII).
-
For max. allowable media temperatures see Technical Data (Section 3).
-
The stored liquids may neither be prone to high viscosity nor to solid matter
secretion; the viscosity of the storage liquid may not exceed 5,000 mm²/s
(at 0°C).
- The following table shows a selection of liquids hazardous to water, which may be
monitored using the specified leak detector.
Liquids not listed here require review in
terms of stability of the media-touching parts of the leak detector (for used materials
refer to Section 6.1) and the connecting components (e.g. connection lines,
condensate vessels, liquid barrier) using the material tables in terms.