background image

1 - 10

In this mode, the compressor will run only if the following
conditions are met:

• Process Control Temperature > Adjustable dew point

value*

• Freeze Protection < 25°F

• High pressure switch closed (no “HiP alarm)

• Dryer on mode

• Delay timer expired

• No high or low temperature* alarms

*If the compressor is on, then the process control
temperature must drop below the process control
temperature set point before the compressor will turn
off.  If the compressor is off, then the process control
temperature must rise above the set point before the
compressor will turn on.

Percent Savings LED

Calculation of savings realized with cycling design com-
pared to direct expansion design. These savings are ex-
pressed in percent of compressor on time to dryer on time.
This mode is display only. No adjustments can be made.

High Pressure “HiP” Alarm

A high pressure alarm occurs if the high pressure switch
opens and the display shows “HiP.” During this condition,
the compressor will shut down. The dryer cannot be re-
started until this switch is manually reset.

To reset the high pressure switch:

1.

Shutdown the dryer per the Shutdown procedure on
page 1-11.

2.

Remove the dryer front panel.

3.

Press the “Manual Reset” switch near the electrical
enclosure.

4.

Replace the dryer front panel.

5.

Restart the dryer according to the Start-up proce-
dure.

If this alarm cannot be reset or occurs frequently, consult
your local representative before servicing the dryer.

AUTOMATIC DRAIN VALVES (ADVs)

Energy Saving Cycling dryers are equipped with an elec-
tronic-timer controlled drain valve (ADV) that automatically
discharges condensate from the dryer. Controls for the dryer
drain valve are on the Controller Membrane Panel.

All models are equipped with a strainer/isolation valve ahead
of the drain valve on the separator. The strainer prevents
large particles from entering the valve. The isolation valve

allows servicing of the strainer and valve without shutting
the dryer down.

The ADV has two LED indicators and a test button to help
verify operation. Pushing the test button causes the drain
port to click open. One LED indicates that power is sup-
plied to the ADV; the other LED indicates that the drain port
is open. The power indicator turns off when the drain port
opens. If either LED fails to turn on at the proper time, refer
to the Maintenance section of this manual. If the dryer is
under warranty, call your local distributor for authorization
before servicing.

To minimize air losses, set the timer so that only air dis-
charges at the end of the open period. Recommended ini-
tial settings are a 3-second drain on time and a 4-minute
drain off time. If air discharges for more than one second,
set the timer for a longer cycle or a shorter opening. If liq-
uid discharges as the port is closing, set the timer for a
shorter cycle or a longer opening.

START-UP

Once the dryer has been installed according to instructions,
it is ready to be operated. The system is fully automatic
and does not require any auxiliary controls. It is designed
to run continuously.

To start the dryer:

Do not start dryer with compressed air flow through the
dryer. Close dryer isolation valves until start-up procedure
is complete.

1.

Supply power to the dryer and disengage Emergency
Stop button. The Power On LED will light indicating
power to the controller. The crankcase heater warmup
will begin (the display will show the number of minutes
remaining in the warmup period). This warmup period
is essential to allow the compressor oil to warm and
boil off liquid refrigerant, preventing compressor fail-
ure. The warmup will be skipped only if the dryer was
started previously and supply power has been off for
less than 60 minutes.

NOTE

The Dryer On LED will blink if the START button is
pressed before the end of the warm-up period.

2.

During the warm-up period, review the INSTALLATION
instructions to make sure the dryer has been properly
installed.

3.

If the dryer is water-cooled, open water supply lines.

4.

After the warm-up period, push the START button. The
Start button energizes the controller for normal opera-
tion.

Summary of Contents for RCD Series

Page 1: ...ESSED AIR DRYERS INSTRUCTION MANUAL Models RCD 200 through RCD 600 E N G L I S H 8610 483 9 Rev A 03 04 Bulletin 18 2 685 2nd Edition 5030C 040313 INTERNAL USE ONLY E N G L I S H INTERNAL USE ONLY E N...

Page 2: ...uling 1 4 Air Cooled Models 1 4 Electrical Installation 1 4 HOW IT WORKS 1 4 Airflow 1 4 Refrigeration System 1 4 ENERGY MANAGEMENT CONTROLLER EMC 1 6 Controller Operation 1 6 Dryer Warmup 1 6 EMC MEM...

Page 3: ...evere in jury or death 4 High voltage in the motor and control box is danger ous The dryer must be installed in accordance with recognized electrical codes Before working on the elec trical system dis...

Page 4: ...our responsibility Handling The dryer is mounted on a base to facilitate moving the dryer with a forklift Forks should extend all the way through the forklift channels provided to reduce stress on the...

Page 5: ...n Table II will cause a rise in dew point unless the dryer inlet air flow is reduced The refrigerant discharge pressure control will shut down the refrigerant compressor if cooling water is inadequate...

Page 6: ...the dryer Confirm that your line voltage is the same as the voltage listed on the data plate Provide disconnect and fuses in accordance with applicable codes Field wiring must com ply with local and...

Page 7: ...PROCESS PORT HIGH SIDE PROCESS PORT CAPILLARY TUBES DISTRIBUTOR AIRFLOW ASSEMBLY OUTLET AIR INLET AIR HPS T Figure 1 Flow Schematic Air Cooled Models CONDENSER AMBIENT AIRFLOW HIGH PRESSURE CUT OUT S...

Page 8: ...ee table below so that the crankcase heater has sufficient time to warm up before starting Warmup Delay Times e m i T f f O r e w o P e m i T y a l e D r e y r D e t u n i m 1 o t 0 s d n o c e s 0 6...

Page 9: ...nctions and starts the dryer i e the Dryer On LED lights STOP Button Push button that deactivates the controller and stops the dryer i e the Dryer On LED is off Up and Down Buttons Used to change the...

Page 10: ...k on The LED will stay lit until the STOP button is pushed Dryer On LED Indicates the dryer is on This light will blink if the START button is pressed during the compressor warm up period Left hand Co...

Page 11: ...value in memory Note All changes will be lost if you do not press the SET button before moving to another display param eter i e pressing the DISPLAY SELECT button Set Auto Drain Off Time Min LED Indi...

Page 12: ...ryer down The ADV has two LED indicators and a test button to help verify operation Pushing the test button causes the drain port to click open One LED indicates that power is sup plied to the ADV the...

Page 13: ...5 Slowly open the customer supplied blowdown inter nal pressure relief valve to vent the internal pressure 6 Close the blowdown valve when internal pressure is 0 psig DANGER Portions of the control c...

Page 14: ...ket from the solenoid coil housing Do not damage or lose the gasket 6 Remove 13mm nut and spring washer from top of so lenoid coil housing 7 Lift solenoid coil housing off solenoid core in valve body...

Page 15: ...e L e g r a h e r d n a r i a p e r k a e l e t a c o L n o i t a r e g i r f e r n i s e l b a s n e d n o c n o n r o r i A r e l l i h c n i k a e l e l b i s s o P m e t s y s e b t s u m r e l l...

Page 16: ...Type Valve Aids in Disconnecting Compressor from the System PRESSURE GUAGE THERMOMETER DRIP LEG MANOMETER DIFFERENTIAL PRESSURE INDICATOR AUTOMATIC DRAIN VALVE FALSE LOADER Blows Off Air Outside of Co...

Page 17: ...5 8 3 4 4 4 1 4 8 6 5 4 6 3 1 2 7 3 5 0 6 2 2 2 0 1 5 5 4 1 9 7 1 3 6 4 0 4 0 1 0 0 3 3 7 8 1 5 7 3 7 2 2 0 1 5 2 0 4 8 7 9 5 8 3 4 4 4 1 4 8 6 5 4 6 3 1 2 7 3 5 0 6 2 2 2 0 1 5 5 4 1 9 7 1 8 7 4 7 6...

Page 18: ...5 6 5 4 e g a t l o V l a n i m o N 0 6 1 0 3 2 8 0 2 e g a t l o V n i M x a M 7 8 1 3 5 2 s p m A d a o L d e t a R 9 0 1 3 0 6 1 9 9 6 1 3 2 9 1 9 7 1 2 s p m A r o t o R d e k c o L 3 9 4 1 8 4 8...

Page 19: ...A 1 REPLACEMENT PARTS WIRING SCHEMATICS...

Page 20: ...A 2 REPLACEMENT PARTS Air Cooled Models 200 600 scfm 9 5 6 8 LEFT VIEW 7 4 TOP VIEW REAR VIEW FRONT VIEW 1 3 2...

Page 21: ...3 8 0 3 G 9 5 0 8 4 0 3 G 4 0 5 9 9 0 3 G 4 0 5 9 9 0 3 G 4 0 5 9 9 0 3 G r o t i c a p a C n u R r o t o M n a F 1 9 0 1 5 0 3 G 1 9 0 1 5 0 3 G 8 5 9 2 6 0 3 G 8 5 9 2 6 0 3 G 8 5 9 2 6 0 3 G 6 0 6...

Page 22: ...A 4 REPLACEMENT PARTS Water Cooled Models 200 600 scfm 10 7 9 LEFT VIEW 6 8 5 4 TOP VIEW REAR VIEW FRONT VIEW 1 3 2...

Page 23: ...C r o s s e r p m o C 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G n o i t p O 3 E 0 6 0 3 2 8 0 2 r o s s e r p m o C 7 5 1 7 6 0 3 G 1 5 8 5 8 0 3 G 2 1 4 0 9 0 3...

Page 24: ...COMPRESSOR FAN 1 2 3 M 1S 28 29 30 EMERGENCY STOP SWITCH HIGH PRESSURE CUT OUT WITH MANUAL RESET HPS 32 27 26 25 J3 KEYBOARD MEMBRANE CONTROLLER ASSEMBLY MCA 8 1 CUTOUT SW COMPRESSOR DRAIN VALVE J6 J...

Page 25: ...TOP SWITCH GND COMPRESSOR FAN 1 2 3 HIGH PRESSURE CUT OUT WITH MANUAL RESET J3 KEYBOARD 1 MEMBRANE CONTROLLER ASSEMBLY MCA 1S DRAIN VALVE 26 25 1SOL 24 23 22 NO COM NC ALARM CONTACTS NO NC UNPOWERED R...

Page 26: ...DRAIN VALVE GND EMERGENCY STOP SWITCH COMPRESSOR FAN 1 2 3 31 M 32 1S HPS HIGH PRESSURE CUT OUT WITH MANUAL RESET 24 23 22 NC COM NO 2TS ALARM CONTACTS NO NC UNPOWERED RATING 5A 115 VAC 5A 24 VDC CHA...

Page 27: ...ECTIONS HERE POP RIVET 3 16 BRACKET INSERT BRACKET TM E6X CONDUIT SEALING RING 1 2 WASHER LOCK PLATED 5 16 WASHER FLAT PLATED 1 4 NUT HEX PLATED 1 4 20 BOLT HEX HEAD PLATED 1 4 20 x 0 5 LG WASHER LOCK...