This alarm will automatically restart when the temperature
falls below 80°F.

Low Temperature Alarm LED

A low temperature alarm will also occur if the freeze pro-
tection temperature drops below 25°F. This alarm occurs
immediately, with no time delay. When a low temperature
alarm occurs, the Low Temperature Alarm LED will light
and the compressor will shut down.

Low temperature alarms will only occur while the dryer is in
“run” mode (dryer on).

This alarm will automatically restart the compressor when
the temperature rises above 30°F.

Display Screen

The right-hand column of LEDs on the controller indicates
the value displayed on the display screen. The default dis-
play is process control temperature and the Process Con-
trol Temperature LED is lit. Each time the DISPLAY SE-
LECT button is pressed, the display will advance to the
next value and the corresponding LED will be lit.

Right-hand Controller LEDs

Process Control Temperature LED

Indicates the display is showing the process control tem-
perature. This temperature is displayed in units of Fahren-
heit or Celsius (depending on which is selected), as indi-
cated by the LEDs on the left-hand column.

Set Auto Drain On Time (Sec) LED

Indicates the display is showing the number of seconds of
auto on time.

To change the auto drain on time:

• Press the DISPLAY SELECT button until the Set Auto

Drain On Time (Sec) LED is lit. The display will show
the current drain on time setting (in seconds).

• Press the up or down button to increase or decrease

the drain on time. The Set Auto Drain On Time (Sec)
LED will blink.

This setting has a minimum value of 1 and a maxi-
mum value of 30. The up and down buttons will “auto
repeat” (from 1 to 30) if held down continuously.

• Once the desired time is displayed, press the SET but-

ton to store the new value in memory.

Note: All changes will be lost if you do not press the
SET button before moving to another display param-
eter (i.e. pressing the DISPLAY SELECT button).

Set Auto Drain Off Time (Min) LED

Indicates the display is showing the number of minutes of
auto off time.

To change the auto drain off time:

• Press the DISPLAY SELECT button until the Set Auto

Drain Off Time (Min) LED is lit. The display will show
the current drain off time setting (in minutes).

• Press the up or down button to increase or decrease

the drain off time. The Set Auto Drain Off Time (Min)
LED will blink.

This setting has a minimum value of 0.5 and a maxi-
mum value of 30. The up and down buttons will “auto
repeat” (from 0.5 to 30) if held down continuously.

• Once the desired time is displayed, press the SET but-

ton to store the new value in memory.

Note: All changes will be lost if you do not press the
SET button before moving to another display param-
eter (i.e. pressing the DISPLAY SELECT button).

Preset Dew Point LED

Allows the operator to select between the preset (factory
set) dew point or an adjusted dew point (see below).

Using the preset dew point, the dryer is set to cycle at the
factory-set conditions. The compressor will run only if the
following conditions are met:

• Process Control Temperature > 36°F*

• Freeze Protection < 25°F

• High pressure switch closed (no “HiP alarm)

• Dryer on mode

• Delay timer expired

• No high or low temperature* alarms

*If the compressor is on, then the process control tem-
perature must drop to 36°F before the compressor will
turn off.  If the compressor is off, then the process con-
trol temperature must rise to 37°F before the compres-
sor will turn on.

When the Preset Dew Point LED is on, the display indi-
cates which set point is being used:

• P = preset dew point

• A = adjustable dew point

Adjustable Dew Point LED

Allows the operator to adjust the process control tempera-
ture set point from 36°F up to 46°F. Hysteresis is still 1°F
about whatever set point is chosen in this ten degree range.

Summary of Contents for RCD Series

Page 1: ...ESSED AIR DRYERS INSTRUCTION MANUAL Models RCD 200 through RCD 600 E N G L I S H 8610 483 9 Rev A 03 04 Bulletin 18 2 685 2nd Edition 5030C 040313 INTERNAL USE ONLY E N G L I S H INTERNAL USE ONLY E N...

Page 2: ...uling 1 4 Air Cooled Models 1 4 Electrical Installation 1 4 HOW IT WORKS 1 4 Airflow 1 4 Refrigeration System 1 4 ENERGY MANAGEMENT CONTROLLER EMC 1 6 Controller Operation 1 6 Dryer Warmup 1 6 EMC MEM...

Page 3: ...evere in jury or death 4 High voltage in the motor and control box is danger ous The dryer must be installed in accordance with recognized electrical codes Before working on the elec trical system dis...

Page 4: ...our responsibility Handling The dryer is mounted on a base to facilitate moving the dryer with a forklift Forks should extend all the way through the forklift channels provided to reduce stress on the...

Page 5: ...n Table II will cause a rise in dew point unless the dryer inlet air flow is reduced The refrigerant discharge pressure control will shut down the refrigerant compressor if cooling water is inadequate...

Page 6: ...the dryer Confirm that your line voltage is the same as the voltage listed on the data plate Provide disconnect and fuses in accordance with applicable codes Field wiring must com ply with local and...

Page 7: ...PROCESS PORT HIGH SIDE PROCESS PORT CAPILLARY TUBES DISTRIBUTOR AIRFLOW ASSEMBLY OUTLET AIR INLET AIR HPS T Figure 1 Flow Schematic Air Cooled Models CONDENSER AMBIENT AIRFLOW HIGH PRESSURE CUT OUT S...

Page 8: ...ee table below so that the crankcase heater has sufficient time to warm up before starting Warmup Delay Times e m i T f f O r e w o P e m i T y a l e D r e y r D e t u n i m 1 o t 0 s d n o c e s 0 6...

Page 9: ...nctions and starts the dryer i e the Dryer On LED lights STOP Button Push button that deactivates the controller and stops the dryer i e the Dryer On LED is off Up and Down Buttons Used to change the...

Page 10: ...k on The LED will stay lit until the STOP button is pushed Dryer On LED Indicates the dryer is on This light will blink if the START button is pressed during the compressor warm up period Left hand Co...

Page 11: ...value in memory Note All changes will be lost if you do not press the SET button before moving to another display param eter i e pressing the DISPLAY SELECT button Set Auto Drain Off Time Min LED Indi...

Page 12: ...ryer down The ADV has two LED indicators and a test button to help verify operation Pushing the test button causes the drain port to click open One LED indicates that power is sup plied to the ADV the...

Page 13: ...5 Slowly open the customer supplied blowdown inter nal pressure relief valve to vent the internal pressure 6 Close the blowdown valve when internal pressure is 0 psig DANGER Portions of the control c...

Page 14: ...ket from the solenoid coil housing Do not damage or lose the gasket 6 Remove 13mm nut and spring washer from top of so lenoid coil housing 7 Lift solenoid coil housing off solenoid core in valve body...

Page 15: ...e L e g r a h e r d n a r i a p e r k a e l e t a c o L n o i t a r e g i r f e r n i s e l b a s n e d n o c n o n r o r i A r e l l i h c n i k a e l e l b i s s o P m e t s y s e b t s u m r e l l...

Page 16: ...Type Valve Aids in Disconnecting Compressor from the System PRESSURE GUAGE THERMOMETER DRIP LEG MANOMETER DIFFERENTIAL PRESSURE INDICATOR AUTOMATIC DRAIN VALVE FALSE LOADER Blows Off Air Outside of Co...

Page 17: ...5 8 3 4 4 4 1 4 8 6 5 4 6 3 1 2 7 3 5 0 6 2 2 2 0 1 5 5 4 1 9 7 1 3 6 4 0 4 0 1 0 0 3 3 7 8 1 5 7 3 7 2 2 0 1 5 2 0 4 8 7 9 5 8 3 4 4 4 1 4 8 6 5 4 6 3 1 2 7 3 5 0 6 2 2 2 0 1 5 5 4 1 9 7 1 8 7 4 7 6...

Page 18: ...5 6 5 4 e g a t l o V l a n i m o N 0 6 1 0 3 2 8 0 2 e g a t l o V n i M x a M 7 8 1 3 5 2 s p m A d a o L d e t a R 9 0 1 3 0 6 1 9 9 6 1 3 2 9 1 9 7 1 2 s p m A r o t o R d e k c o L 3 9 4 1 8 4 8...

Page 19: ...A 1 REPLACEMENT PARTS WIRING SCHEMATICS...

Page 20: ...A 2 REPLACEMENT PARTS Air Cooled Models 200 600 scfm 9 5 6 8 LEFT VIEW 7 4 TOP VIEW REAR VIEW FRONT VIEW 1 3 2...

Page 21: ...3 8 0 3 G 9 5 0 8 4 0 3 G 4 0 5 9 9 0 3 G 4 0 5 9 9 0 3 G 4 0 5 9 9 0 3 G r o t i c a p a C n u R r o t o M n a F 1 9 0 1 5 0 3 G 1 9 0 1 5 0 3 G 8 5 9 2 6 0 3 G 8 5 9 2 6 0 3 G 8 5 9 2 6 0 3 G 6 0 6...

Page 22: ...A 4 REPLACEMENT PARTS Water Cooled Models 200 600 scfm 10 7 9 LEFT VIEW 6 8 5 4 TOP VIEW REAR VIEW FRONT VIEW 1 3 2...

Page 23: ...C r o s s e r p m o C 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G n o i t p O 3 E 0 6 0 3 2 8 0 2 r o s s e r p m o C 7 5 1 7 6 0 3 G 1 5 8 5 8 0 3 G 2 1 4 0 9 0 3...

Page 24: ...COMPRESSOR FAN 1 2 3 M 1S 28 29 30 EMERGENCY STOP SWITCH HIGH PRESSURE CUT OUT WITH MANUAL RESET HPS 32 27 26 25 J3 KEYBOARD MEMBRANE CONTROLLER ASSEMBLY MCA 8 1 CUTOUT SW COMPRESSOR DRAIN VALVE J6 J...

Page 25: ...TOP SWITCH GND COMPRESSOR FAN 1 2 3 HIGH PRESSURE CUT OUT WITH MANUAL RESET J3 KEYBOARD 1 MEMBRANE CONTROLLER ASSEMBLY MCA 1S DRAIN VALVE 26 25 1SOL 24 23 22 NO COM NC ALARM CONTACTS NO NC UNPOWERED R...

Page 26: ...DRAIN VALVE GND EMERGENCY STOP SWITCH COMPRESSOR FAN 1 2 3 31 M 32 1S HPS HIGH PRESSURE CUT OUT WITH MANUAL RESET 24 23 22 NC COM NO 2TS ALARM CONTACTS NO NC UNPOWERED RATING 5A 115 VAC 5A 24 VDC CHA...

Page 27: ...ECTIONS HERE POP RIVET 3 16 BRACKET INSERT BRACKET TM E6X CONDUIT SEALING RING 1 2 WASHER LOCK PLATED 5 16 WASHER FLAT PLATED 1 4 NUT HEX PLATED 1 4 20 BOLT HEX HEAD PLATED 1 4 20 x 0 5 LG WASHER LOCK...

Page 28: ......

Page 29: ...a l p s i D e t a D e m i T y B n i a r D o t u A e v l a V l i O p m o C l e v e L n O r e w o P h g i H e r u t a r e p m e T m r a l A w o L e r u t a r e p m e T m r a l A s s e c o r P s l o r t...

Page 30: ...a l p s i D e t a D e m i T y B n i a r D o t u A e v l a V l i O p m o C l e v e L n O r e w o P h g i H e r u t a r e p m e T m r a l A w o L e r u t a r e p m e T m r a l A s s e c o r P s l o r t...

Page 31: ......

Page 32: ...D IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRI...

Reviews: