13-25-600 Page 34
Figure 4-5 – EXAMPLE LABEL
Note: Transformer secondary fuse and decal do not require replacement. Refer to the
transformer wiring diagram, located on side of transformer and as illustrated in attachment 5
of this instruction, to ensure proper transformer primary wiring connections.
9. Locate the motor starter electronic relay (
“OL” as shown on the applicable, attached wiring
diagram), and adjust the relay according to the actual motor nameplate amperage times the
service factor of the motor. Adjustment is performed by turning the adjustment dial located on the
overload relay.
10. Open compressor package enclosure to locate the electric motor terminal (connection) box.
Disconnect and reconnect motor wiring connections inside the terminal box, for the supply
voltage, according to motor wiring diagram located inside, or near, the motor terminal box cover.
Pay attention that no foreign objects, such as dirt or metal dust, fall down into the terminal box or
wiring while the terminal box is open. Close the terminal box and reassemble the compressor
enclosure.
11. Upon power being applied, verify controller is energized and test/jog motor to ensure proper
rotation
.
ATTACHMENT 3
Summary of Contents for AirSmart Controller APEX5-15A
Page 11: ...13 25 600 Page 10 Figure 1 2 COMPRESSOR ILLUSTRATION 303ELA797 B Ref Drawing Page 1 of 2...
Page 27: ...13 25 600 Page 26 Figure 4 1 CONTROL SCHEMATIC 300ELA797 B Ref Drawing...
Page 37: ...13 25 600 Page 36 300ELA546 B Ref Drawing Page 2 of 2...
Page 39: ...13 25 600 Page 38 301ELA546 B Ref Drawing Page 2 of 2...
Page 41: ...13 25 600 Page 40 304ELA546 B Ref Drawing Page 2 of 2...
Page 43: ...13 25 600 Page 42 305ELA546 B Ref Drawing Page 2 of 2...
Page 45: ...13 25 600 Page 44 309ELA546 B Ref Drawing Page 2 of 2...