background image

PROCEDURE 7—COOLING

The blower speed may be field adjusted to deliver required airflow for cooling application (see Table 5).

PROCEDURE 8—CONSTANT BLOWER SWITCH

This furnace is equipped with a constant low-speed blower option. Whenever room thermostat is not calling for heating or cooling, blower runs
on low speed in order to provide air circulation. If constant blower option is not desired, the rocker switch on side of control box may be used
to turn off constant speed.

CARE AND MAINTENANCE

WARNING: The ability to properly perform maintenance on this equipment requires certain expertise, mechanical

skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other
than those procedures recommended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS PERSONAL INJURY, OR DEATH.

WARNING: Before performing any service functions, unless operations specifically require power to be on, make sure

all utilities are turned off upstream of appliance. Failure to comply with this warning will cause a fire hazard and/or bodily
harm.

WARNING: To avoid personal injury, make sure the electrical supply power is off before servicing.

PROCEDURE 1—GENERAL

In order to keep furnace in good operating condition and to maintain it’s warranty, furnace MUST be serviced on an annual basis. This servicing
includes a nozzle change, burner inspection, visual check of tube passages through flue outlet and cleanout ports, and a visual inspection of
combustion chamber when burner is removed.
Depending on above inspection, service could also include cleaning and vacuuming of heat exchanger tubes and possibly heat exchanger drum
section.
Removal of any heat exchanger components which are sealed by gaskets requires replacement of gasket.

WARNING: Failure to replace any heat exchanger gaskets with new gaskets when any heat exchanger plates or covers

are removed could lead to heat exchanger leakage, sooting, and/or a hazardous condition capable of causing bodily harm.

This furnace should never be operated without air filter(s). Disposable filters should be replaced at least once a year. If equipped to provide cooling,
filters should be replaced a minimum of twice a year. Permanent filters should be cleaned at least twice a year.
ALWAYS KEEP MAIN OIL VALVE TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME.

PROCEDURE 2—OIL BURNER

Contact your service technician for service.
Lubricate burner motor with SAE 10 oil. Once each year, pour 2 teaspoons of oil slowly into each oil cup.
To maintain proper performance, oil nozzle MUST be replace once a year.

Fig. 1–Fan Off Time DIP Switch Settings (Black Box Represents Switch Position)

A95115

1

2

60 Sec

1

2

90 Sec

DELAY  OFF  DIP  SWITCH  SETTINGS

1

2

1

2

1

2

120 Sec

1

2

150 Sec

Table 5–Airflow Data (CFM)

UNIT SIZE

BLOWER SPEED

EXTERNAL STATIC PRESSURE IN. WC

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

036105

High

1795

1735

1675

1605

1550

1485

1425

1350

1275

1220

Medium

1365

1335

1305

1275

1255

1215

1155

1105

1050

985

Low

995

965

945

925

900

870

825

775

725

670

048125

High

1905

1845

1770

1695

1630

1565

1490

1425

1325

1220

Medium

1750

1675

1620

1560

1500

1440

1370

1305

1235

1130

Low

1390

1350

1305

1260

1220

1180

1120

1060

985

880

060155

High

2025

1960

1905

1850

1800

1665

1575

1500

1415

1315

Medium

1885

1825

1760

1705

1640

1565

1500

1430

1350

1265

Low

1555

1490

1445

1410

1350

1280

1230

1155

1085

1005

1. Airflow values in cubic ft. per minute (CFM) rounded to nearest 5 CFM.

2. Data taken without filters in place.

—8—

Summary of Contents for PO8LAA

Page 1: ...OIL CONNECTIONS 6 BAROMETRIC DRAFT CONTROL 6 ELECTRICAL 6 FILTERS 6 OPERATIONAL CHECKOUT 6 START UP 6 RECOMMENDED INSTALLATION PRACTICES AND COMBUSTION CHECK 7 FAN ADJUSTMENT CHECK 7 LIMIT CONTROL CH...

Page 2: ...of above codes should be used and are available from either The National Fire Protection Agency Batterymarch Park Quincy MA 02269 or The Canadian Standards Association 178 Rexdale Blvd Rexdale Ontari...

Page 3: ...regulator included with furnace shall be installed in same room or enclosure as furnace in such a manner as to prevent any difference in pressure between regulator and combustion air requirements Air...

Page 4: ...impose proper static at outlet of furnace 2 A flexible duct connector of noncombustible material should be installed at unit on both supply and return air systems In applications where extremely quie...

Page 5: ...ey flue is clear of any dirt or debris 2 Be sure that chimney is not servicing an open fireplace 3 Never reduce pipe size below minimum certified furnace pipe size shown in Table 2 4 All pipe should b...

Page 6: ...conduit where required used may terminate at side panel of unit It is not necessary to extend conduit inside unit from side panel to control box When replacing any original furnace wiring use only 105...

Page 7: ...e nozzle oil pressures of 100 psig The firing rate noted on nameplate may be obtained with standard nozzles by adjusting pump pressure as noted in Table 4 or on label on furnace On a new installation...

Page 8: ...ubes and possibly heat exchanger drum section Removal of any heat exchanger components which are sealed by gaskets requires replacement of gasket WARNING Failure to replace any heat exchanger gaskets...

Page 9: ...and vacuum cleaner 6 Before reinstalling cleanout port covers the gasket on each cover MUST be replaced Use cleanout port gasket kit part no 20196201 7 Reinstall covers and tighten in place making sur...

Page 10: ...er forward out of heat exchanger Be careful not to bump combustion chamber as it becomes brittle after having been fired 17 Use a stiff brush and vacuum cleaner to clean inside of primary drum 18 Befo...

Page 11: ...d on inside of louvered door to properly rewire unit PROCEDURE 5 KEEPING FILTERS CLEAN WARNING Never operate unit without a filter or with filter access door removed Failure to adhere to this warning...

Page 12: ...epth Height A B C D E F G H 036105 22 52 33 20 17 1 4 6 25 1 4 18 048125 22 57 33 20 22 1 4 6 30 1 4 18 060155 22 57 33 20 22 1 4 6 30 1 4 18 A96309 INSULATION INTERMEDIATE PANEL FILTER B A G D ELECTR...

Page 13: ...Fig 6 Barometric Damper Locations A95117 FIG A FIG G FIG D FIG L FIG B FIG C FIG J FIG H FIG K POOR WRONG WRONG WRONG WRONG WRONG BAROMETRIC DAMPER LOCATIONS GOOD LOCATIONS BAD LOCATIONS 13...

Page 14: ...DES IN CANADA WIRING MUST CONFORM TO CURRENT CSA 22 1 CANADIAN ELECTRICAL CODE PART 1 AND OR LOCAL CODES 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED...

Page 15: ...15...

Page 16: ...2000 CAC BDP P O Box 70 Indianapolis IN 46206 impo8l03 16 Catalog No 63PO 8LI...

Reviews: