background image

2. One sq. in. per 4000 Btuh of total input rating when air is brought in through vertical ducts.

3. One sq. in. per 2000 Btuh of total input rating when air is transferred through horizontal ducts.

When ducts are used to supply air, they must be of the same cross-sectional area as free area of openings to which they connect.

The minimum dimension of rectangular air ducts must not be less than 3 in.

In calculating free area, consideration shall be given to blocking effect of louvers, grilles, or screens protecting openings. Screens used shall not
be smaller than 1/4in. mesh and shall be readily accessible for cleaning. If free area through a design of louver or grille is know, it shall be used
in calculating size design and free area specified. If design and free areas are not known, it may be assumed that wood louvers have 20 percent
free area and metal louvers and grilles have 60 percent free area. Louvers shall be fixed in open position or interlocked with furnace so they open
automatically at furnace start-up and remain open during furnace operation.

WARNING: Do not block combustion air openings in the furnace. Any blockage will result in improper combustion

which may result in a fire hazard and/or cause bodily harm.

The lack of proper amount of combustion air can lead to serious furnace operational problems. Some of these problems are:

1. Excessive oil burner after drip and oil fumes.

2. Sooting.

3. Melted oil burner couplings and/or ignitor/relay control.

4. A condition where air band or air shutter settings must be open more than normal to achieve proper combustion.

5. Lockouts on start-up.

PROCEDURE 2—DUCT WORK RECOMMENDATIONS

The proper sizing of warm air ducts is necessary to ensure satisfactory furnace operation. Duct work should be in accordance with the latest editions
of NFPA-90A (Installation of Air Conditioning and Ventilating Systems) and NFPA-90B (Warm Air Heating ad Air Conditioning Systems) or
Canadian equivilent.

The supply duct work should be attached to flanged opening provided at discharge end of furnace. See Fig. 5 for dimensions of this opening.

The following recommendations should be followed when installing duct work:

1. Install locking-type dampers in all branches of individual ducts to balance out system. Dampers should be adjusted to impose proper static

at outlet of furnace.

2. A flexible duct connector of noncombustible material should be installed at unit on both supply and return air systems. In applications where

extremely quiet operation is neccessary, the first 10 ft (if possible) of supply and return ducts should be internally lined with acoustical
material.

3. In cases where return-air grille is located close to fan inlet, there should be at least one 90° air turn between fan inlet and grille. Further

reduction in sound level can be accomplished by installing acoustical air turning vanes or lining duct as described in item 2 above.

4. When a single air grille is used, duct between grille and furnace must be the same size as return opening in furnace.

CAUTION: Return-air grilles and warm air registers MUST not be obstructed.

WARNING: When supply ducts carry air circulated by furnace to areas outside spaces containing furnace, return-air

MUST also be handled by a duct sealed to furnace casing and terminating outside space containing furnace. Incorrect duct
work termination and sealing will create a hazardous condition which could lead to bodily harm.

When installing furnace with cooling equipment for year-round operation, the following recommendations must be followed for series or parallel
airflow:

1. In series airflow applications, coil is mounted after furnace in an enclosure in supply-air stream. The furnace blower is used for both heating

and cooling airflow.

WARNING: The coil MUST be installed on air discharge side of furnace. Under no circumstances should airflow be

such that cooled, conditioned air can pass over furnace heat exchanger. This will cause condensation in heat exchanger and
possible failure of heat exchanger which could lead to fire harzard and/or a hazardous condition which may lead to bodily
harm. Heat exchanger failure due to improper installation may not be covered by warranty.

2. In parallel airflow applications, dampers must be provided to direct air over furnace heat exchanger when heat is desired and over cooling

coil when cooling is desired.

IMPORTANT:

The dampers should be adaquate to prevent cooled air from entering furnace. If manually operated, dampers must be equipped

with a means to prevent operation of either cooling unit or furnace unless damper is in full cool or heat position.

INSTALLATION

PROCEDURE 1—VENTING INSTRUCTIONS

Venting of furnace should be to the outside and in accordance with local codes or requirements of local utility.

—4—

Summary of Contents for PO8LAA

Page 1: ...OIL CONNECTIONS 6 BAROMETRIC DRAFT CONTROL 6 ELECTRICAL 6 FILTERS 6 OPERATIONAL CHECKOUT 6 START UP 6 RECOMMENDED INSTALLATION PRACTICES AND COMBUSTION CHECK 7 FAN ADJUSTMENT CHECK 7 LIMIT CONTROL CH...

Page 2: ...of above codes should be used and are available from either The National Fire Protection Agency Batterymarch Park Quincy MA 02269 or The Canadian Standards Association 178 Rexdale Blvd Rexdale Ontari...

Page 3: ...regulator included with furnace shall be installed in same room or enclosure as furnace in such a manner as to prevent any difference in pressure between regulator and combustion air requirements Air...

Page 4: ...impose proper static at outlet of furnace 2 A flexible duct connector of noncombustible material should be installed at unit on both supply and return air systems In applications where extremely quie...

Page 5: ...ey flue is clear of any dirt or debris 2 Be sure that chimney is not servicing an open fireplace 3 Never reduce pipe size below minimum certified furnace pipe size shown in Table 2 4 All pipe should b...

Page 6: ...conduit where required used may terminate at side panel of unit It is not necessary to extend conduit inside unit from side panel to control box When replacing any original furnace wiring use only 105...

Page 7: ...e nozzle oil pressures of 100 psig The firing rate noted on nameplate may be obtained with standard nozzles by adjusting pump pressure as noted in Table 4 or on label on furnace On a new installation...

Page 8: ...ubes and possibly heat exchanger drum section Removal of any heat exchanger components which are sealed by gaskets requires replacement of gasket WARNING Failure to replace any heat exchanger gaskets...

Page 9: ...and vacuum cleaner 6 Before reinstalling cleanout port covers the gasket on each cover MUST be replaced Use cleanout port gasket kit part no 20196201 7 Reinstall covers and tighten in place making sur...

Page 10: ...er forward out of heat exchanger Be careful not to bump combustion chamber as it becomes brittle after having been fired 17 Use a stiff brush and vacuum cleaner to clean inside of primary drum 18 Befo...

Page 11: ...d on inside of louvered door to properly rewire unit PROCEDURE 5 KEEPING FILTERS CLEAN WARNING Never operate unit without a filter or with filter access door removed Failure to adhere to this warning...

Page 12: ...epth Height A B C D E F G H 036105 22 52 33 20 17 1 4 6 25 1 4 18 048125 22 57 33 20 22 1 4 6 30 1 4 18 060155 22 57 33 20 22 1 4 6 30 1 4 18 A96309 INSULATION INTERMEDIATE PANEL FILTER B A G D ELECTR...

Page 13: ...Fig 6 Barometric Damper Locations A95117 FIG A FIG G FIG D FIG L FIG B FIG C FIG J FIG H FIG K POOR WRONG WRONG WRONG WRONG WRONG BAROMETRIC DAMPER LOCATIONS GOOD LOCATIONS BAD LOCATIONS 13...

Page 14: ...DES IN CANADA WIRING MUST CONFORM TO CURRENT CSA 22 1 CANADIAN ELECTRICAL CODE PART 1 AND OR LOCAL CODES 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED...

Page 15: ...15...

Page 16: ...2000 CAC BDP P O Box 70 Indianapolis IN 46206 impo8l03 16 Catalog No 63PO 8LI...

Reviews: