4.
Remove the burner access panel by removing the
seven (7) No. 10 sheet metal screws that secure the
panel to the cabinet. Be careful
not
to damage the
rubber seal strips that are attached to the cabinet
(behind the access panel).
5.
Remove the No. 10 sheet metal screws that secure
the manifold seal plate and gasket to the bottom of
the burner box. The plate and gasket are assembled
onto the manifold pipe and will not come completely
loose, but will slide down the manifold pipe in order
to provide clearance for manifold removal.
6.
Disconnect wires from rollout switch.
7.
Remove manifold or burner/manifold assembly.
Manifold ONLY
a.
Remove the No. 10 screws that secure the
manifold pipe to both legs of the manifold
assembly.
The manifold pipe must be
supported during this step, or it could fall and
damage the furnace or cause bodily injury!
b.
Slide the manifold pipe (with valve and orifice)
forward, out of the furnace.
Burner/Manifold Assembly
a.
Remove the No. 10 screws that secure the
burner/manifold assembly legs to the furnace.
The manifold pipe must be supported during
this step, or it could fall and damage the
furnace or cause bodily injury!
b.
Slide the burner/manifold assembly forward, out
of the furnace until the assembly is clear of the
manifold retention pins.
c.
Rotate the assembly slightly, in order for the legs
to clear the sides of the cabinet, and remove
through the front of the furnace.
8.
To reinstall the manifold pipe or burner/manifold
assembly, reverse the above steps. When replacing
the manifold seal plate to the bottom of the burner
box, be sure the gasket is not torn so a proper seal
is achieved. Also insure that the sealing strips for the
burner access panel are in position and undamaged,
in order to prevent air leaks around the door.
Blower Removal/Replacement:
Removal
1.
Turn OFF all electrical power to the furnace.
2.
Remove the control box access panel and blower
access panel.
3.
Unplug wires from the blower assembly to the control
box.
4.
Remove the four (4) screws securing the control box
in the unit (two (2) in the cabinet at the sides of the
blower door opening and two (2) at the top rear of the
control box). Be sure to support the control box so
that it does not fall!
5.
Rotate the control box out of the cabinet and support
it so that no strain is placed on any wiring. It may be
necessary to disconnect the electrical supply and
thermostat wiring from the control board.
6.
Remove the blower retaining screws from the front of
each blower leg (See Figure 34). These are the two
(2) screws located in the blower compartment that
secure the blower legs to the blower partition panel.
7.
Slide the blower forward about two (2) inches. This
will disengage the rear of the blower legs from the
blower partition. Rotate the front of the blower down
to clear the control box mounting tabs on the
underside of the blower partition, and continue sliding
the blower forward until it is out of the unit. Take
care to clear the control box mounting tabs.
Replacement
1.
Place the blower in the blower opening of the unit.
2.
Slide the blower back, into the unit, taking care to
clear the control box mounting tabs.
3.
When the blower is about halfway into the cabinet,
rotate the rear of the blower UP so that the rear of
the blower legs engage the side rails in the blower
partition.
4.
Continue sliding the blower into the unit until the front
of the blower housing is behind the control box
mounting tabs. Rotate the front of the blower UP
until the legs lie flat against the bottom of the blower
partition, then slide blower fully into position. The
rear of the blower should be against the stop in the
partition and the rear of the blower legs should be
under the partition.
5.
Reattach the two (2) blower securing screws, the
control box, any disconnected wiring, the blower
access panel, and the control box access panel.
Lubricating Motors:
Direct drive motor and blower assemblies are factory
lubricated and normally do not require oiling. If oiling is
required lubrication of the blower motor is to be
preformed only by a qualified service agency.
Figure 34
BLOWER REMOVAL AND REPLACEMENT
20558801
Issue 0442
Page 30 of 32
Summary of Contents for Gas-Fired Furnace
Page 13: ...FURNACE WIRING SPECIFICATIONS 20558801 Issue 0442 Page 5 of 32 ...
Page 21: ...Figure 8 20558801 Issue 0442 Page 13 of 32 VENT TERMINATION CLEARANCES ...
Page 36: ...SEQUENCE OF OPERATION DIRECT IGNITION SYSTEM CONTROL 20558801 Issue 0442 Page 28 of 32 ...
Page 40: ...WIRING DIAGRAM 20558801 Issue 0442 Page 32 of 32 ...