Version 1, 15 June 2020, 4 of 16 

5.0 

WATER SUPPLY CONDITIONS  

5.1  

INTRODUCTION 

This mixing valve cabinet assembly is manufactured to the highest standards and has approval to AS4032.1 
which permits it to be installed in healthcare establishments such as hospitals, nursing homes and residential 
care homes.  When installed in healthcare establishments the supply conditions detailed in Table 2 must be 
observed and the commissioning and servicing requirements detailed on section 7 & 8 must be followed.

 

5.2  

SUPPLY PRESSURE REQUIREMENTS 

This mixer is designed to be installed on all types of plumbing systems. 

Hot  and  cold  water  supply  pressures  should  be  reasonably  balanced;  however,  the  mixer  will  function  within 
specification on unequal pressures up to 6:1. 
The  mixer  has  integral  isolating  valves  which  permit  servicing  of  the  strainer,  check  valve/flow  regulator  and 
thermostatic cartridge. They are also used for thermal disinfection. 

The  minimum  pressure  for  the  correct  thermal  operation  is  20kPa.    However,  to  achieve  an  acceptable  flow 
performance at very low pressures it may be necessary to remove the combined check valve and flow regulators 
and replace them with simple check valves to facilitate thermal disinfection. 

Working Temperature Range (°C) 

Min 

Max 

90 

Working Pressure Range (kPa) 

Min 

20 

Max 

500 

Maximum Static Pressure (kPa) 

1000 

Permitted Supply Pressure Variation 

6:1 

Table 2. 

Water supply conditions 

Note:

 Tapware must be installed in accordance with the provisions of AS/NZS 3500. Installations not 

complying with AS/NZS 3500 may void the product and performance warranty provisions. 

 

 

Summary of Contents for 101.10.70.10

Page 1: ...ng tempered water to the desired outlets This stainless steel hinged cabinet kit is a lockable cabinet with 20mm copper fittings 2 in and 1 out which allows secure installation and safe simple mainten...

Page 2: ...es 3 0 DESCRIPTION This manual covers the CliniMix Lead SafeTM TMV SS Cabinet Assembly with Universal Door 20 Bottom In Out These are designed to provide tempered water to the desired outlets This mix...

Page 3: ...APH The Galvin Engineering CliniMix Thermostatic Mixing Valve is suitable for many applications The Head loss Characteristic for Mixed Outlet Flow rate versus Balanced Inlet Pressure is shown below in...

Page 4: ...ction within specification on unequal pressures up to 6 1 The mixer has integral isolating valves which permit servicing of the strainer check valve flow regulator and thermostatic cartridge They are...

Page 5: ...ure to do this may void the warranty 3 Connect water lines Before connecting to water lines all lines must be flushed Remove protective vinyl cap from copper tubes Join each copper tube to the correct...

Page 6: ...rtest length of pipe work between the mixing valve and outlet fixture Allow the mixed outlet to flow for at least 60 seconds to allow the temperature to stabilise before taking a temperature reading a...

Page 7: ...Restore the cold water to the TMV After the mixed water temperature has stabilized note the outlet temperature ensuring the outlet temperature has reestablished Now repeat the above test except this t...

Page 8: ...st plugs in the top of the inlet fittings are tight and that there is no evidence of water leakage The TMV must then be recommissioned as per Section 7 0 including temperature adjustment and the shutd...

Page 9: ...rass top assembly screw out the plastic spindle and replace the smaller O ring 5 Carefully remove the spindle from the center of the body 6 Remove O ring from spindle Replace with O ring supplied in t...

Page 10: ...OR WM TMV1 1 2 WM ISO 1 INLET ISOLATOR ELBOWS PAIR FOR WM TMV1 1 3 WM NRV 1 INLET NON RETURN VALVE FOR WM TMV1 PAIR 1 4 WM STR 1 INLET STRAINERS FOR WM TMV1 PAIR 1 5 WM TPKIT 1 THERMOSTAT PISTON SHUTT...

Page 11: ...r s recommendation the ode and all relevant statutory and local tate or erritory requirements 4 The TMV must be returned to Galvin Engineering together with a fully and correctly completed Galvin Engi...

Page 12: ...ntrol valves to ensure inlet conditions are within range Clean strainers ensuring debris is removed Either full hot or cold flowing from the outlet fixture Valve is incorrectly set Hot Cold water has...

Page 13: ...___________________ Model No ________________________ Size _________ Valve Location Building _____________________________________________________________________ Valve Identification No _____________...

Page 14: ...k It is hereby certified that all the commissioning work has been carried out by the undersigned in accordance with the requirements of the Codes of Practice indicated prior Date of Valve Commissioned...

Page 15: ...Outlets in Use One Outlet in Use All Req d Outlets in Use 1 2 3 4 5 6 7 8 9 10 11 Give details of brand and model designation Commensurate with the design flow rate for the mixing valve Note An accura...

Page 16: ...e ______________________ Date _______________________ Maintenance Tests Yes Date of Previous Service ______________________________________________________________________ Previous Service carried out...

Reviews: