- 8 -
OPERATION MANUAL AND WARRANTY CARD
"Galmet Sp. z o.o.”
10.1. Installing the heat pump indoors
The heat pump must be installed in a way allowing a service technician to maintain the
compressor unit and should provide access to at least to one wall of the device. A minimum
distance from the wall should be 40 cm. A minimum floor area needed to install the heat
pump is 2 x 2 m (4 square meters), while the room height should exceed 2.2 m. When
installing the device without ducts carrying the air to the outside of the building provide a
minimum room ventilation at a level of 350 m³/h.
C
D
A
B
A+B <10m
C >800mm
D > 400mm
HEAT PUMP
45°
Cold water
Coil return
Coil supply
Circulation
Domestic hot water
Sensor
Fig. 5 Heat pump installation
10.2. Heat pump positioning inside the boiler room
Air ducts
Utility room,
e.g. laundry
room, garage
HEAT PUMP
45°
Cold water
Coil return
Coil supply
Circulation
Domestic hot water
Sensor
Fig. 6 Heat pump positioning inside the boiler room
The minimum length between the suction duct and cold air outlet should be
1.5 m !!