ESTRO BLDC
10 ACCESSORIES
Bv - Auxiliary water drip tray for vertical
installation units
The auxiliary drip tray is used to collect the
condensate from the valve and the pressure
regulator. It can be used on all éstro fan coils.
BH - Auxiliary water drip tray for horizontal
installation units
The BH auxiliary drip tray is suitable for
horizontal installation fan coils to collect the
condensate from the ON/OFF 3-way valve (VK
S accessory).
RE - Electric heating element complete with
installation kit, safety devices and power
relay box
Designed to meet the needs of supplement
conventional water heating systems,the kit
includes armoured electric heating elements,
safety thermostats (with automatic/manual
resetting) and power relay set.
The additional heating element should be
coupled to the MYCOMFORT LARGE control panel.
KSC - Condensate drainage pump kit
It permits the drainage of condensate in case
of height differences. The pump is equipped
with a check valve on the drain pipe and is
capable to drain up to 8 l/h of water.
RA / RM - Inlet and outlet connectors
These accessories are designed for éstro BLDC
FCI, FFI fan coils and are used for room ducts
when the basic unit (éstro BLDC FCI) is placed
within false ceilings and/or recess wall mounted.
For each configuration, the inlet and outlet
connectors are available in straight version and
in 90° jointed version.
GIvK - valve insulation shell
The GIVK valve insulation shell avoids the
creation of condensate within the valve body.
The plumbing connections are provided either
on the right side or the left side.
MCSWE - Water temperature sensor for
microprocessor controls model MYCOMFORT
Directly connected to the microprocessor control
model
MYCOMFORT
to measure the water
temperature through the heat exchanger.
If the temperature detected is less than 17°C, the unit
will operate in the cooling mode and the controller
will use the summertime temperature scale (19 - 31°C); if the temperature
detected is greater than 37°C the unit will function in the heating mode and
the controller will use the wintertime temperature scale (14 / 26°C). If the
temperature detected by the probe is in the range of 17°C to 37°C, the
controller will inhibit operation of the fan coil unit.
MCSUE - Humidity sensor for on-board
microprocessor controls model MYCOMFORT
LARGE.