2.3  Cabling

The Gallagher T10 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm

2

) stranded 

security cable.  This cable allows the transmission of data (2 wires) and power (2 wires).  When 

using a single cable to carry both power supply and data, both the power supply voltage drop 

and data requirements must be considered.  Although the reader is specified to operate at 9 

Vdc, for good engineering design it is recommended that the voltage at the reader should be 

approximately 12 Vdc.

 

HBUS cabling topology

The HBUS communications protocol is based on the RS485 standard and allows the reader to 

communicate over a distance of up to 500 m (1640 ft).

The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or 

"Star" topology should not be used between devices).  Should "Star" or "Home-Run" wiring be 

required, the HBUS 4H/8H Modules and the HBUS Door Module allow multiple HBUS devices to 

be individually wired to the one physical location.

The end devices on the HBUS cable should be terminated using 120 ohms resistance.  To 

terminate the Gallagher Controller 6000, connect the supplied on-board termination jumpers 

to the Controller.  To terminate a reader, connect the orange (termination) wire to the green 

(HBUS A) wire.  Termination is already included at the HBUS Module, (i.e. each HBUS port is 

permanently terminated at the module).

Connect the on-board 

termination jumper

Controller 6000

RS485 1

HBUS

 

Device

"T" or "Star" circuits are 

not permitted between 

HBUS devices

HBUS

 

Device

Terminate

HBUS

 

Device

HBUS

 

Device

HBUS

 

Device

HBUS

 

Device

HBUS

 

Device

HBUS

 

Device

Terminate

Remove the on-board 

termination jumper

RS485 1

"T" or "Star" circuits are 

not permitted between 

HBUS devices

HBUS

 

Device

Terminate

HBUS

 

Device

Controller 6000

Summary of Contents for C300400

Page 1: ...0 Reader Edition 1 August 2016 Copyright Gallagher Group Limited Gallagher T10 Reader Installation Note T10 Mifare Reader Black C300400 T10 Mifare Reader White C300401 T10 PIV Reader Black C305400 T10...

Page 2: ...ess and it should not be relied on as such To the extent permitted by law all express or implied or other representations or warranties in relation to the information are expressly excluded Neither Ga...

Page 3: ...2016 Copyright Gallagher Group Limited Contents 1 Introduction 4 2 Before you begin 4 3 Distance between readers 7 4 Installation 7 5 LED indications 9 6 Accessories 10 7 Technical specifications 10 8...

Page 4: ...s protocol to communicate with the Gallagher Controller IMPORTANT HBUS compatibility HBUS communications are supported with sites running Gallagher Command Centre vEL7 00 software or later IMPORTANT P...

Page 5: ...i e A T or Star topology should not be used between devices Should Star or Home Run wiring be required the HBUS 4H 8H Modules and the HBUS Door Module allow multiple HBUS devices to be individually wi...

Page 6: ...ELDEN 9842 shielded 2 twisted pair Each 2 x 0 2 mm2 24 AWG 500 m 1640 ft 200 m 650 ft 100 m 330 ft SEC472 4 x 0 2 mm2 Not twisted pairs 24 AWG 400 m 1310 ft 200 m 650 ft 100 m 330 ft SEC4142 4 x 0 4 m...

Page 7: ...tal surface The recommended mounting height for the reader is 1 1 m 3 6 ft from the floor level to the centre of the reader device However this may vary in some countries and you should check local re...

Page 8: ...oller 6000 A Cardax IV Reader connects to a Gallagher Controller 6000 Gallagher 4R 8R Module attached to a Controller 6000 Gallagher GBUS Universal Reader Interface Gallagher GBUS URI Gallagher Contro...

Page 9: ...teps 8 Configure the reader in Command Centre If the reader is connected as an HBUS Reader refer to the topic Configuring HBUS Devices in the Command Centre Configuration Client Online Help If the rea...

Page 10: ...0 7 Technical specifications Routine maintenance Not applicable for this reader Cleaning This reader should only be cleaned with a clean lint free damp cloth Voltage 9 Vdc 16 Vdc Current Idle 1 Maximu...

Page 11: ...frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occu...

Page 12: ...gust 2016 Copyright Gallagher Group Limited 9 Mounting dimensions IMPORTANT This picture is not to scale therefore use the measurements provided 115 mm 4 53 35 mm 1 38 44 mm 1 73 40 mm 1 57 13 mm 1 2...

Reviews: