Specifications
Number
of
Inputs
6
Thermocouple
Inputs
Thermocouple input – Analog Input Map
TC[0:5] = AI[0:5]
Range
Type
K
(default)
0
–
345
deg
C
1
Type
E
0
–
230
deg
C
Type
J
0
–
270
deg
C
Type
T
0
–
345
deg
C
Voltage
Constant
2
Type
K
(default)
10.15
mV/deg
C
Type E
15.225 mV/deg C
Type J
12.925 mV/deg C
Type T
10.15 mV/deg C
1
Contact Galil if required temperatures are outside of listed ranges.
2
Voltage Constant will change if Range is modified
Wiring
The SCB-483x6 has qty 6 thermocouple inputs. The thermocouples interfacing to the SCB-483x6 must have
an Ungrounded or Exposed Junction; contact Galil if Grounded Junction (Figure 17) thermocouples are
required. The wiring of the thermocouple to the SCB-483x6 is shown in Figure 16 below.
Figure 16: Thermocouple Wiring to SCB-483x6
Figure 17: Grounded Thermocouple Input - Not supported with SCB-483x6
98 A2 – SCB-48306/48316
RIO-47xxx