Connecting to Main Power (AC Models)
Before you Begin
l
AMC AC controllers are intended to be supplied in Europe by AC power with a 16A rated over cur-
rent protective device and 2 poles disconnecting device (circuit breaker) or with 20A over current
protective device and 2 poles disconnecting device (UL 489 circuit breaker) in the US and North
America. This device is to be suitably located and easily reached and marked as the disconnecting
device for the equipment. The circuit breaker shall meet the requirements of IEC 60947-1 and IEC
60947-3 and be suitable for the application.
l
Use only the built-in transformer.
l
In case the controller is supplied with a power supply cable connected to it, the controller is for
indoor installations only!
l
Power supply cable should be Outdoor rated, suitable for the installation site, and should comply
with IEC 60227 or IEC 60245 for Europe or ANSI/UL 817 and CSA C22.2 No. 21 for USA and Canada.
l
Power supply cable rating: 250VAC, 1A: -30°C ~ +120°C or 115VAC, 1A: -30°C ~ +120°C depends on
the controller’s actual model.
l
Power supply cord cables yellow and green are for ground connection only.
l
If the supply cord is damaged, it must be replaced by the manufacturer or service agent or a sim-
ilarly qualified person in order to avoid hazard.
l
In order to use the controller for outdoor installation, a licensed electrician must disconnect the
power supply cable, and connect the controller according to the instructions given in the install-
ation chapter of this document and in compliance with all the safety instructions and the local
standards for High Voltage out-door connection.
l
In order to use the controller for outdoor installation, a licensed electrician must disconnect the
power supply cable, and connect the controller according to the instructions given in the install-
ation chapter of this document and in compliance with all the safety instructions and the local
standards for High Voltage out-door connection.
l
If the plug doesn’t comply with your local regulation it must be replaced with suitable plug by
licensed electrician only. Please note that opening additional cable holes in the controller’s housing
bottom plate should be done by drilling only and not by hammering the knock-outs!
l
It is necessary to connect a two-pole switch between the power supply and the controller 115VAC
or 230VAC (depends on the actual controller model).
l
The supply point 115VAC or 230VAC (depends on the actual controller model), the circuit and con-
nection to the transformer must be performed according to “Field Electrical Regulations” by a
licensed electrician who is accredited with a license according to the Electrical Bill and security
requirements.
l
When using an internal transformer, minimal wire diameter must be 0.7mm. Check with standard
measuring equipment that there is no voltage in the electric circuit.
Connecting to Power
1. Route an AC power cable through the cable gland at the bottom side of the cabinet.
The cable range should be Ø4-Ø7 mm.
2. Connect the wires to the transformer wires located inside the cabinet. The Controller units are
supplied with a built in terminal strip.
See "Terminal Strips Drawings" on page 11 for wiring diagrams.
20
AMC Flushing
Controller
User
Guide
Installation
Summary of Contents for AMC-6DC
Page 1: ...AMC Flushing Controller User Guide Revision 1 0 August 2016...
Page 10: ...Installation 2...
Page 12: ...Flushing Controller Model AMC 6AC 230V 12 AMC FlushingController User Guide Installation...
Page 14: ...Flushing Controller Model AMC 12DC 16 AMC FlushingController User Guide Installation...
Page 16: ...Flushing Controller Model AMC 12AC 115V 16 AMC FlushingController User Guide Installation...
Page 47: ......
Page 48: ...AT1602...