3) CONNECTION TO POWER SUPPLY
It is essential to connect to a current socket proportioned to the power of the installed battery charger.
Ensure to also correctly connect the
earth conductor.
If the mains fuse breaks, it must be replaced ONLY AFTER HAVING IDENTIFIED AND SOLVED THE
CAUSE OF THE BREAKAGE and ONLY WITH AN IDENTICAL FUSE.
MODEL
HFS 27C
(4 kW)
Absorbed
Current
(230 V)
AC Fusible
MAINS CABLE
(A)
A
mm²
24
110
15,5
2xCF 16
3x4.0
24
120
16,9
2xCF 16
3x4.0
24
130
18,31
2xCF 16
3x4.0
24
140
19,72
2xCF 16
3x4.0
36
70
14,79
2xCF 16
3x4.0
36
80
16,9
2xCF 16
3x4.0
36
90
19,02
2xCF 16
3x4.0
48
60
16,9
2xCF 16
3x4.0
48
70
19,72
2xCF 16
3x4.0
Tab 3.1
MODEL
HFS 27C
(5 kW)
Absorbed
Current
(230 V)
AC Fusible
MAINS CABLE
(A)
A
mm²
24
160
22,54
2xCF 16
3x6.0
36
100
21,13
2xCF 16
3x6.0
48
85
23,95
2xCF 16
3x6.0
Tab 3.2
MODEL
HFS 27C
(6 kW)
Absorbed
Current
(230 V)
AC Fusible
MAINS CABLE
(A)
A
mm²
24
200
28,17
2xCF 16
3x6.0
36
120
25,36
2xCF 16
3x6.0
48
90
25,36
2xCF 16
3x6.0
48
100
28,17
2xCF 16
3x6.0
80
40
18,78
2xCF 16
3x4.0
80
50
23,48
2xCF 16
3x6.0
80
60
28,17
2xCF 16
3x6.0
Tab 3.3