Installation Instructions
8
General Settings
The General settings MUST be configured after
installation by the installer to ensure correct operation.
It is important to configure the off peak times correctly.
The HHR allows you to configure two separate off peak
charge periods; Period 1 via P01 & P02 and Period 2
via P03 & P04. If you only have one charge period then
set P03 and P04 to 00:00.
To enter the general settings menu turn ON the heater
via the switch at the right side of the heater while
holding down the moon button at the same time. ST will
be displayed, at this point you can release the moon
button.
Use the and buttons to move down and up the
menu options.
To look or change each setting, press and release the
moon button and then use the and
buttons to adjust. Press the moon button to set.
The default settings are as follows:-
ST
: Initial % of storage charge
:
80
P01
: Start time of off peak period 1
:
00:00
P02
: End time of off peak period 1
:
07:00
P03
: Start time of off peak period 2
:
00:00
P04
: End time of off peak period 2
:
00:00
P05
: Ambient sensor offset ±5°C
:
0.0
P06
: Max. working hours of balancing element :
5
P07
: Over temperature protection °C
:
2
P08
: Display temp. Centigrade or Fahrenheit :
°C
Open
: Open window detection option
:
Off
To skip through P05, P06, P07, P08 and Open options
simply press and release the plus button until you exit
back to displaying the temperature.