3.9.DEFAULT SETTINGS:
By pushing the clock key
at the same time as we turn on the heater with the power switch, located at the right-side
panel, software resets to the default settings. Four horizontal blinking segments will appear in the screen to confirm it.
The default programming, all time intervals in frost protection temperature level are set.
Default Values
Sun
: Comfort temperature
21ºC
Moon
: Economic temperature
18ºC
St
: Initial % of storage charge
80%
P01
: Starting time off peak period 1
00:00
P02
: Ending time off peak period 1
07:00
P03
: Starting time off peak period 2
00:00
P04
: Ending time off peak period 2
00:00
P05
: Ambient sensor Offset
0ºC
P06
: Max. Balance resistance
–
working period
5 hours
P07
: Overtemperature protection
2ºC
P08
: Temperature Unit
ºC
Open
: Open Window Detection Function
Off
Default Programming
Frost Protection 24h*7
Frost protection temperature
3ºC (Fixed value)
Incorrect time settings, erroneous programming of the reduced rate time and too high temperature settings may result in
a high cost of your electricity bill.
4.- TROUBLESHOOTING
HHR does not heat
Please check it is connected and switched on.
Make sure the device is not covered or the lower air inlets are not obstructed. The LR safety limit
may be activated; in this case, it is necessary to rearm it manually. Please contact technician.
HHR does not reach set up
temperature
Make sure that adequate temperature is selected.
Make sure the heater is sized correctly for heat loss.
ERR 1 in display
Ambient temperature sensor trouble, please contact technician.
ERR 2 in display
Air outlet temperature sensor trouble, please contact technician.
ERR 3 in display
Core temperature sensor trouble, please contact technician.
Keyboard does not respond
If display shows [ - - ] when pressing a key, the
display is blocked. Press the “+”
and “
-
” key at the
same time for three seconds to unblock it.