9
D5032
- SIL 3 Switch/Proximity Detector Repeater Relay Output
G.M. International ISM0108-11
ON
D5032S
A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode.
WARNING:
Dip-switch 7-8 must be set to “OFF” position.
Configuration
Dip switch configuration
1
2
3
4
7-8 must be set to "OFF" position
3-4-6 Not used
5
6
7
8
ON
CH
Setting
Line fault
detection
IN / OUT
Operation
NO-NE or
NC-ND
NO-ND or
NC-NE
Disabled
(switch / proximity sensor)
Enabled
(proximity sensor or switch
with end of line resistors,
de-energizes relay in fault condition)
1
OFF
5
OFF
1
ON
5
ON
Input Input
Input
Input
7
NO
8
OR
NC
7
8
7
NO
8
OR
NC
7
8
Output
NE
Output
NE
Output
ND
Output
ND
Position in fault condition
2
ON
2
OFF
1
2
3
4
5
6
7
8
ON
Dip switch factory settings. All Switches are OFF
For SIL Application
For SIL Application