background image

 

D5032 

- SIL 3 Switch/Proximity Detector Repeater Relay Output 

G.M. International ISM0108-11 

ON 

 

Configuration 

Dip switch configuration 

1

2

3

4

5

6

7

8

ON

Must be set to 

"OFF" position

D5032D used as duplicator or fault output 

A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode. 

 

WARNING:

  Terminals 9-10 must be shorted to set module as Duplicator or Fault Out. 

   

Dip-switch 3 must be set to “OFF” position. 

Fault condition 

1

1

8

7

6

8

7

4

4

CH 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

Output 1 

NO-NE or 

NC-ND 

NO-ND or 

NC-NE 

Duplicator 

Parallel 

Mode 

Reverse 

Mode 

Fault 

Output 

OFF 

 

 

ON 

 
 

OFF 

ND 

Mode 

NE 

Mode 

ON 

OFF 

OFF 

 

 

ON 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, 

de-energizes relay in fault condition) 

No Fault 

No Fault 

1

 

OFF 

5

OFF 

5

ON 

 

Output 2 

Operation 

Input Input 

Output 1 

Input 

Output 1 

Input 

 

NO 

OR 

NC 

 

NO 

OR 

NC 

NE 

ND 

Output 1 

ND 

Output 1 

NE 

NE 

ND 

Set SW4 

equal to 

SW2 

Set SW4 

opposite to 

SW2 

6

6

 

          ON 
 
De-energized in 
fault condition if 
line fault detection 
enabled (SW1 ON) 
 
     
          OFF 
 
Not specified fault condition 

Position in fault 

condition 

 

          ON 
 
Output 1, 
De-energized in 
fault condition 
 
 
          OFF 
 
Output 1, not specified fault condition 

Position in fault 

condition 

Fault condition 

 

 

2

ON 

2

OFF 

1

2

3

4

5

6

7

8

ON

Dip switch factory settings. All Switches are OFF 

For SIL Application 

For SIL Application 

For SIL Application 

For SIL Application 

For SIL Application 

For SIL Application 

For SIL Application 

For SIL Application 

Summary of Contents for D5032D

Page 1: ...SIL 3 Switch Proximity Detector Repeater Relay Output G M International ISM0108 11 SIL 3 Switch Proximity Detector Repeater Relay Output Termination Board Models D5032S D5032D D5032S D5032D INSTRUCTION MANUAL ...

Page 2: ...ort circuit Output voltage free SPST relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA Mechanical Electrical life 5 106 1 106 operation typical Operate Release time 8 4 ms typical Bounce time NO NC contact 3 8 ms typical Frequency response 10 Hz maximum Compatibility CE mark compliant conforms ...

Page 3: ...ation in Zone 2 NO NC switch proximity Detector Input NE ND relay actuation mode Field open and short circuit detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system In field programmability by DIP Switch ATEX IECEx UL C UL FM FMC INMETRO EAC EX UKR TR n 898 NEPSI TÜV Certifications TÜV Functional Safety Certification ...

Page 4: ... group See parameters indicated in the table below D5032 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5032 Terminals D5032 Associated Apparatus Parameters Cenelec US Ci Ci device C cable IIC A B Co Ca 2 4 µF Co Ca 16 8 µF Co Ca 75 µF IIB C IIA D For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 of the ...

Page 5: ... Supply 24 Vdc Out 1 SIL3 Out 2 SIL 3 F 9 10 In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection MODEL D5032D Duplicator or Fault Out 7 8 Termination board connector Supply 24 Vdc Out 1 SIL3 Out 2 Duplicator or Fault F 9 10 In Proximity voltage ...

Page 6: ...ween a condition of contact close open and a line open short circuit fault Installation D5032 series are Switch Proximity Detector Interface housed in a plastic enclosure suitable for installation on customized Termination Board D5032 unit can be mounted with any orientation over the entire ambient temperature range Electrical connection of conductors up to 2 5 mm are accommodated by polarized plu...

Page 7: ...isabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NE ND Output ND Output NE Position in fault condition 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sen...

Page 8: ...FF ON OFF ND Mode NE Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output 2 Operation Input Input Output 1 Input Output 1 Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NE ND Output 1 ND Output 1 NE NE ND Set SW4 equal to SW2 Set SW4 opposite to SW2 6 6 ON De energi...

Page 9: ...figuration 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 1 OFF 5 OFF 1 ON 5 ON Input Input Input Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 Output NE Output NE Output ND O...

Page 10: ...ndition ON ON ON 1 IN OUT Operation SW2 NO NE or NC ND ON NO ND or NC NE for SIL application OFF Channel 1 2 SW4 ON OFF D5032D used as double channel Configuration Summary Table WARNING dip switch 6 7 8 must be set to OFF position Output 2 Operation SW6 SW7 SW8 Mode SW4 Duplicator De energized in fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL ...

Reviews: