10
D5032
- SIL 3 Switch/Proximity Detector Repeater Relay Output
G.M. International ISM0108-11
Line fault detection
SW1
Disabled
(switch/proximity sensor)
OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
ON
SW5
OFF
ON
IN/OUT Operation
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
D5032S Configuration Summary Table
WARNING:
Dip-switch 7-8 must be set to “OFF” position.
D5032D (used as duplicator or fault output) Configuration Summary Table
WARNING:
Terminals 9-10 must be shorted to set module as Duplicator or Fault Out. Dip-switch 3 must be set to “OFF” position.
Channel
2
Line fault detection
SW1
SW5
SW3
Disabled
(switch/proximity sensor)
OFF OFF OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
ON ON ON
1
IN/OUT Operation
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
Channel
1
2
SW4
ON
OFF
D5032D (used as double channel) Configuration Summary Table
WARNING:
dip-switch 6-7-8 must be set to “OFF” position.
Output 2 Operation
SW6
SW7 SW8
Mode
SW4
Duplicator
De-energized in
fault condition
(for SIL application)
if line fault
detection enabled
(SW1 ON)
ON
OFF ON
Parallel
(for SIL
applicatio
n)
Set equal
to SW2
Not specified
Fault condition
OFF Reverse
Set opposite
to SW2
OFF
(for SIL application)
ON OFF
ND ON
NE
(for SIL
applicatio
n)
OFF
Fault Output
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
OFF OFF OFF OFF OFF OFF OFF OFF
DIP Switch factory settings (valid for D5032S and D5032D)
Configuration
IN/OUT Operation Output 1
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
Line fault detection
SW1
SW5
Disabled
(switch/proximity sensor)
OFF
OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
Output 1,
(for SIL application)
De-energized in Fault condition
ON
Output 1,
Not specified Fault condition
OFF
ON