10 

D5032 

- SIL 3 Switch/Proximity Detector Repeater Relay Output 

G.M. International ISM0108-11 

Line fault detection 

SW1 

Disabled 

(switch/proximity sensor)  

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON 

SW5 

OFF 

ON 

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE 

(for SIL application) 

OFF 

D5032S Configuration Summary Table 

 

WARNING:

  Dip-switch 7-8 must be set to “OFF” position. 

D5032D (used as duplicator or fault output) Configuration Summary Table 

 

WARNING:

 Terminals 9-10 must be shorted to set module as Duplicator or Fault Out. Dip-switch 3 must be set to “OFF” position. 

Channel 

Line fault detection 

SW1 

SW5 

SW3 

Disabled 

(switch/proximity sensor) 

OFF OFF OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON ON ON 

1  

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE  

(for SIL application) 

OFF 

Channel 

SW4 

ON 

OFF 

D5032D (used as double channel) Configuration Summary Table 

 

WARNING:

 dip-switch 6-7-8 must be set to “OFF” position. 

Output 2 Operation 

SW6 

SW7  SW8 

Mode 

SW4 

Duplicator 

De-energized in 
fault condition 
(for SIL application) 
if line fault 
detection enabled 
(SW1 ON) 

ON 

OFF ON 

Parallel 
(for SIL 

applicatio

n) 

Set equal 

to SW2 

Not specified 
Fault condition 

OFF Reverse 

Set opposite 

to SW2 

OFF 

(for SIL application) 

ON OFF 

ND ON 

NE 

(for SIL 

applicatio

n) 

OFF 

Fault Output 

SW1  SW2  SW3  SW4  SW5  SW6  SW7  SW8 

OFF OFF OFF OFF OFF OFF OFF OFF 

DIP Switch factory settings (valid for D5032S and D5032D)

 

Configuration 

IN/OUT Operation Output 1 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE 

(for SIL application) 

OFF 

Line fault detection 

SW1  

SW5 

Disabled 

(switch/proximity sensor)  

OFF  

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

Output 1,  

(for SIL application) 

De-energized in Fault condition 

ON 

Output 1, 

Not specified Fault condition 

OFF 

ON  

Summary of Contents for D5032D

Page 1: ...SIL 3 Switch Proximity Detector Repeater Relay Output G M International ISM0108 11 SIL 3 Switch Proximity Detector Repeater Relay Output Termination Board Models D5032S D5032D D5032S D5032D INSTRUCTION MANUAL ...

Page 2: ...ort circuit Output voltage free SPST relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA Mechanical Electrical life 5 106 1 106 operation typical Operate Release time 8 4 ms typical Bounce time NO NC contact 3 8 ms typical Frequency response 10 Hz maximum Compatibility CE mark compliant conforms ...

Page 3: ...ation in Zone 2 NO NC switch proximity Detector Input NE ND relay actuation mode Field open and short circuit detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system In field programmability by DIP Switch ATEX IECEx UL C UL FM FMC INMETRO EAC EX UKR TR n 898 NEPSI TÜV Certifications TÜV Functional Safety Certification ...

Page 4: ... group See parameters indicated in the table below D5032 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5032 Terminals D5032 Associated Apparatus Parameters Cenelec US Ci Ci device C cable IIC A B Co Ca 2 4 µF Co Ca 16 8 µF Co Ca 75 µF IIB C IIA D For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 of the ...

Page 5: ... Supply 24 Vdc Out 1 SIL3 Out 2 SIL 3 F 9 10 In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection MODEL D5032D Duplicator or Fault Out 7 8 Termination board connector Supply 24 Vdc Out 1 SIL3 Out 2 Duplicator or Fault F 9 10 In Proximity voltage ...

Page 6: ...ween a condition of contact close open and a line open short circuit fault Installation D5032 series are Switch Proximity Detector Interface housed in a plastic enclosure suitable for installation on customized Termination Board D5032 unit can be mounted with any orientation over the entire ambient temperature range Electrical connection of conductors up to 2 5 mm are accommodated by polarized plu...

Page 7: ...isabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NE ND Output ND Output NE Position in fault condition 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sen...

Page 8: ...FF ON OFF ND Mode NE Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output 2 Operation Input Input Output 1 Input Output 1 Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NE ND Output 1 ND Output 1 NE NE ND Set SW4 equal to SW2 Set SW4 opposite to SW2 6 6 ON De energi...

Page 9: ...figuration 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 1 OFF 5 OFF 1 ON 5 ON Input Input Input Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 Output NE Output NE Output ND O...

Page 10: ...ndition ON ON ON 1 IN OUT Operation SW2 NO NE or NC ND ON NO ND or NC NE for SIL application OFF Channel 1 2 SW4 ON OFF D5032D used as double channel Configuration Summary Table WARNING dip switch 6 7 8 must be set to OFF position Output 2 Operation SW6 SW7 SW8 Mode SW4 Duplicator De energized in fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL ...

Reviews: