background image

 

D1073 

- SIL 2 Temperature Signal Converter and Trip Amplifiers 

G.M. International ISM0019-13 

 

Start-up 

 

Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed 
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, output signal should be corresponding to the input from the 
sensor, alarm LED should reflect the input variable condition with respect to trip points setting. If possible change the transmitter output and check the corresponding Safe Area output. 

Installation 

 

D1073 is a temperature signal converter and trip amplifiers housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022. 
D1073 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" 
Instruction Manual D1000 series for detailed instructions. 
D1073 temperature signal converter operates at low level measuring signals, for best performance, install it far from heat sources (heat dissipating equipment) and 
wide temperature excursions, in example at the bottom of a cabinet with heat dissipating equipment, if any, at the top. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit 
without suffering or causing any damage 

(for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing)

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “3” and negative at terminal “4”. 
Connect positive output of analog channel at terminal “1” and negative output at “2”. 
Connect trip amplifier output of alarm A at terminal “5” and “6” and trip amplifier output of alarm B at terminal “7” and “8”. 
For a thermocouple temperature input, connect thermocouple positive extension wire at terminal “15”, negative and shield (if any) at terminal “16”. 
Make sure that compensating wires have the correct metal and thermal e.m.f. and are connected to the appropriate thermocouple terminal, note that a wrong compensating cable type or 
a swapped connection is not immediately apparent but introduces a misleading measurement error that appears as a temperature drift. For a 3 wires thermoresistance temperature input 
connect thermometer wire A at terminal “16”, B and C interconnected wires at “14” and “13”. 
Note that for a correct line resistance compensation in case of 3 wire sensor, wire A and B should have the same resistance. 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards 
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
Connect SPST alarm contacts checking the load rating to be within the contact maximum rating (2 A, 250 V, 500 VA 80 W resistive load). 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1073 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D1073 series must be connected to SELV or SELV-E supplies. 
Relay output contact must be connected to loads non exceeding category I, pollution degree I overvoltage limits. 

Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential. 

Summary of Contents for D1073S

Page 1: ...D1073 SIL 2 Temperature Signal Converter and Trip Amplifiers ISM0019 13 D1073S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Temperature Signal Converter And Trip Amplifiers Din Rail Model D1073S ...

Page 2: ...max 600 Ω load source mode current limited at 22 mA or 0 1 to 5 V or 0 2 to 10 V signal limited at 11 V Resolution 2 µA current output or 1 mV voltage output Transfer characteristic linear or reverse on mV or transmitting potentiometer temperature linear or reverse on temperature sensors Response time 50 ms 10 to 90 step change Output ripple 20 mVrms on 250 Ω load Alarm Trip point range within rat...

Page 3: ... resistance compensation Reference Junction Compensation automatic or fixed programmable value 0 4 20 mA 0 1 5 V 0 2 10 V Output Signal temperature linear or reverse 16 characters tag Two independent trip amplifiers Output for burnout detection Common burnout detection available when using Power Bus enclosure High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Co...

Page 4: ...ntation if the device is Intrinsically Safe check its suitability for the Hazardous Area Hazardous Locations and gas group encountered and that its maximum allowable voltage current power Ui Vmax Ii Imax Pi Pi are not exceeded by the safety parameters Uo Voc Io Isc Po Po of the D1073 Associated Apparatus connected to it Also consider the maximum operating temperature of the field device check that...

Page 5: ...S LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 For SIL applications alarm contacts must be used in series with equal configuration Relay contact shown in de energized position MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 13 14 15 16 5 6 7 8 Alarm A Alarm B Set A Set B In 1 3 wire RTD 4 wire RTD Pot MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vd...

Page 6: ...connect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative Any unauthorized modification must be avoided Warning Operation Input channel of D1073 accepts a ...

Page 7: ...ocouple positive extension wire at terminal 15 negative and shield if any at terminal 16 Make sure that compensating wires have the correct metal and thermal e m f and are connected to the appropriate thermocouple terminal note that a wrong compensating cable type or a swapped connection is not immediately apparent but introduces a misleading measurement error that appears as a temperature drift F...

Page 8: ...e value obtained from the section Technical Data Considering the 1 3 load power and the 70 above discussed the power effectively dissipated internally by the isolators can therefore become of the actual power delivered by the power supply Digital barriers dissipate all the supply power inside the enclosure consequently the total power dissipation into a cabinet with mixed analog and digital barrie...

Page 9: ...value press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key 7 Sens 3 Level Menu Displays the input sensor type configuration Press Enter to set the input sensor press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key you can choose betwee...

Page 10: ...essed Enter key you can choose between 5 different alarm conditions press Select key to change the type and then the Enter key to confirm the choice The condition types are OFF no alarm detection the relay output is always in normal condition HI high alarm condition the relay output change status when an alarm condition is detected input variable goes above the set value LO low alarm condition the...

Page 11: ...n type Fixed only range from 60 to 100 C RTD line resist line resistance error compensation value thermoresistance only range from 5 to 20 Ω INPUT TAG SECTION OUTPUT SECTION Output analog output type 4 20 mA current output range from 4 to 20 mA 0 20 mA current output range from 0 to 20 mA 1 5 V voltage output range from 1 to 5 V 0 5 V voltage output range from 0 to 5 V 2 10 V voltage output range ...

Reviews: