D1073 

- SIL 2 Temperature Signal Converter and Trip Amplifiers 

G.M. International ISM0019-13 

PPC1090 Operation 

The Pocket Portable Configurator type PPC1090 is suitable to configure the “smart” barrier of D1000 series. The PPC1090 unit is not ATEX, UL or FM approved and is only to be used in 
Safe Area/Non Hazardous Locations and prior to installation of the isolator and prior to connection of any I.S. wiring. Do not use PPC1090 configurator in Hazardous Area/Hazardous 
Locations. The PPC1090 configurator is powered by the unit (no battery power) when the telephone jack is plugged into the barrier (RJ12 6 poles connection type with 1:1 connection). 
It has a 5 digit display, 4 leds and four push buttons with a menu driven configuration software and can be used in Safe Area/Non Hazardous Locations without any certification because 
it plugs into the non intrinsically safe portion of circuit. 

 

PPC1090 Configuration 

The configuration procedure follows a unit specific menu. The display shows the actual menu item, the led shows the channel configured and the push button actuates as “Enter”, 
“Select”, “Down” and “Up” key. The “Enter” key is pressed to confirm the menu item, the “Select” key is pressed to scroll the menu item, the “Down” and “Up” keys are pressed to 
decrement or increment the numeric value of menu item. The “Up” key is also pressed to decrement the menu level. When the PPC1090 is plugged into the unit, the display shows the 
barrier model (first level menu). Then press the “Enter” key to the second level menu and the “Select” key to scroll the menu voice. When the selected menu item is displayed press the 
“Enter” key to confirm the choice. Follow this procedure for every voice of the menu. When a numeric menu item is to be changed, press the “Select” key to highlight the character and 
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key. To return to a higher level menu press the “Up” key. 

 

1) 

D1073S

   

 

[1 Level Menu] 

Displays Model D1073S single channel temperature signal converter and trip amplifiers. Press “Enter” key to second level menu. 

2) 

CF

 

 

 

[2 Level Menu] 

Displays the parameters configuration menu. Press “Enter” key to configure the functional parameters, press the “Select” key to the next menu 
level item or “Up” key to return to first level. 

3) 

In

 

 

 

[2 Level Menu] 

Displays the input variable monitoring. Press “Enter” to display the current input value reading, press the “Select” key to the next menu level 
item or “Up” key to return to first level. 

4) 

Out

 

 

 

[2 Level Menu] 

Displays the analog output variable monitoring. Press “Enter” to display the current output value reading, press the “Select” key to the next 
menu level item or “Up” key to return to first level. 

5) 

Set A

 

 

 

[3 Level Menu] 

Displays the SET A Trip Point Value configuration. Press “Enter” to set the trip point value, press the “Select” key to the next menu level item or 
“Up” key to return to second level. If you pressed “Enter” key, you can set the set value; press the “Select” key to highlight the character you 
want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

6) 

Set B

 

 

 

[3 Level Menu] 

Displays the SET B Trip Point Value configuration. Press “Enter” to set the trip point value, press the “Select” key to the next menu level item or 
“Up” key to return to second level. If you pressed “Enter” key, you can set the set value; press the “Select” key to highlight the character you 
want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key 

7) 

Sens

 

 

 

[3 Level Menu] 

Displays the input sensor type configuration. Press “Enter” to set the input sensor, press the “Select” key to the next menu level item or “Up” key 
to return to second level. If you pressed “Enter” key, you can choose between 26 different sensors; press “Select” key to change the input 
sensor and then the “Enter” key to confirm the choice. The input sensors are: 
Tc B 

 

Thermocouple type B, -10 to +1800°C range 

Tc E 

 

Thermocouple type E, -250 to +1000°C range 

Tc J 

 

Thermocouple type J, -200 to +750°C range 

Tc K 

 

Thermocouple type K, -250 to +1350°C range 

Tc L 

 

Thermocouple type L, -200 to +800°C range 

Tc N 

 

Thermocouple type N, -200 to +1300°C range 

Tc R 

 

Thermocouple type R, -50 to +1750°C range 

Tc S 

 

Thermocouple type S, -50 to +1750°C range 

Tc T 

 

Thermocouple type T, -250 to +400°C range 

Tc U 

 

Thermocouple type U, -200 to +400°C range 

Tc LR   

Thermocouple type LR (russian standard), -200 to +800°C range 

Pt 100   

Thermoresistance Pt 100 

 with 0.385 coefficient, -200 to +850°C range 

PP 100   

Thermoresistance Pt 100 

 with 0.392 coefficient, -200 to +625°C range 

M 100   

Thermoresistance Pt 100 

 with 0.391 coefficient (russian standard), -200 to +650°C range 

M 50 

 

Thermoresistance Pt 50 

 with 0.391 coefficient (russian standard), -200 to +650°C range 

Ni 100   

Thermoresistance Ni 100 

, -50 to +180°C range 

Ni 120   

Thermoresistance Ni 120 

, (russian standard), -75 to +300°C range 

CU 100   

Thermoresistance Copper 100 

 (russian standard), -50 to +200°C range 

CU 53   

Thermoresistance Copper 53 

 (russian standard), -50 to +180°C range 

CU 50   

Thermoresistance Copper 50 

 (russian standard), -50 to +200°C range 

Pot 

 

Potentiometer, 0 to 100% range 

E dc 

 

mV dc input from externally powered transmitter, -20 to +85mV range 

Pt 200   

Thermoresistance Pt 200 

 with 0.385 coefficient, -150 to +400°C range 

Pt 300   

Thermoresistance Pt 300 

 with 0.385 coefficient, -150 to +250°C range 

Tc A1 

 

Thermocouple type A1 (russian standard), -10 to +2500°C range 

Tc A2 

 

Thermocouple type A2 (russian standard), -10 to +1800°C range 

Tc A3 

 

Thermocouple type A3 (russian standard), -10 to +1800°C range 

Tc S1 

 

Thermocouple type S (russian standard), -50 to +1600°C range 

CU 46   

Thermoresistance Copper 46 

 (russian standard), -200 to +650°C range 

 

8) 

Lead

 

 

 

[3 Level Menu] 

Displays the input sensor connection type configuration for thermoresistance sensor. Press “Enter” to set the input connection type, press the 
“Select” key to the next menu level item or “Up” key to return to second level. If you pressed “Enter” key, you can choose between 2 different 
sensor connection; press “Select” key to change the input connection and then the “Enter” key to confirm the choice. The input connection types are: 
3 ter 

 

3 wire connection type thermoresistance 

4 ter 

 

4 wire connection type thermoresistance 

9) 

CJ Typ

   

 

[3 Level Menu] 

Displays the reference junction compensation type configuration for thermocouple sensor. Press “Enter” to set the input compensation type, 
press the “Select” key to the next menu level item or “Up” key to return to second level. If you pressed “Enter” key, you can choose between 2 
different sensor compensation types; press “Select” key to change the type and then the “Enter” key to confirm the choice. 
The input compensation types are: 
CJ Aut   

automatic compensation of ambient temperature (via option 91 thermoresistance sensor) 

CJ Set   

fixed ambient temperature compensation, value is setted by CJ Ref menu item (do not require option 91 thermoresistance sensor) 

Menu item description 

D1073S Menu 

 

Summary of Contents for D1073S

Page 1: ...D1073 SIL 2 Temperature Signal Converter and Trip Amplifiers ISM0019 13 D1073S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Temperature Signal Converter And Trip Amplifiers Din Rail Model D1073S ...

Page 2: ...max 600 Ω load source mode current limited at 22 mA or 0 1 to 5 V or 0 2 to 10 V signal limited at 11 V Resolution 2 µA current output or 1 mV voltage output Transfer characteristic linear or reverse on mV or transmitting potentiometer temperature linear or reverse on temperature sensors Response time 50 ms 10 to 90 step change Output ripple 20 mVrms on 250 Ω load Alarm Trip point range within rat...

Page 3: ... resistance compensation Reference Junction Compensation automatic or fixed programmable value 0 4 20 mA 0 1 5 V 0 2 10 V Output Signal temperature linear or reverse 16 characters tag Two independent trip amplifiers Output for burnout detection Common burnout detection available when using Power Bus enclosure High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Co...

Page 4: ...ntation if the device is Intrinsically Safe check its suitability for the Hazardous Area Hazardous Locations and gas group encountered and that its maximum allowable voltage current power Ui Vmax Ii Imax Pi Pi are not exceeded by the safety parameters Uo Voc Io Isc Po Po of the D1073 Associated Apparatus connected to it Also consider the maximum operating temperature of the field device check that...

Page 5: ...S LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 For SIL applications alarm contacts must be used in series with equal configuration Relay contact shown in de energized position MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 13 14 15 16 5 6 7 8 Alarm A Alarm B Set A Set B In 1 3 wire RTD 4 wire RTD Pot MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vd...

Page 6: ...connect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative Any unauthorized modification must be avoided Warning Operation Input channel of D1073 accepts a ...

Page 7: ...ocouple positive extension wire at terminal 15 negative and shield if any at terminal 16 Make sure that compensating wires have the correct metal and thermal e m f and are connected to the appropriate thermocouple terminal note that a wrong compensating cable type or a swapped connection is not immediately apparent but introduces a misleading measurement error that appears as a temperature drift F...

Page 8: ...e value obtained from the section Technical Data Considering the 1 3 load power and the 70 above discussed the power effectively dissipated internally by the isolators can therefore become of the actual power delivered by the power supply Digital barriers dissipate all the supply power inside the enclosure consequently the total power dissipation into a cabinet with mixed analog and digital barrie...

Page 9: ...value press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key 7 Sens 3 Level Menu Displays the input sensor type configuration Press Enter to set the input sensor press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key you can choose betwee...

Page 10: ...essed Enter key you can choose between 5 different alarm conditions press Select key to change the type and then the Enter key to confirm the choice The condition types are OFF no alarm detection the relay output is always in normal condition HI high alarm condition the relay output change status when an alarm condition is detected input variable goes above the set value LO low alarm condition the...

Page 11: ...n type Fixed only range from 60 to 100 C RTD line resist line resistance error compensation value thermoresistance only range from 5 to 20 Ω INPUT TAG SECTION OUTPUT SECTION Output analog output type 4 20 mA current output range from 4 to 20 mA 0 20 mA current output range from 0 to 20 mA 1 5 V voltage output range from 1 to 5 V 0 5 V voltage output range from 0 to 5 V 2 10 V voltage output range ...