FWE R-AS-10 Operating Instructions Manual Download Page 10

TROUBLESHOOTING GUIDE

19

FWE 

REFRIGERATED "AIRSCREEN" SERIES

18

 

FWE Operating Instructions | Refrigerated "AirScreen" Series

TROUBLESHOOTING GUIDE

FWE 

REFRIGERATED "AIRSCREEN" SERIES

TROUBLESHOOTING GUIDE

 

(CONTINUED)

6.  Condensing unit operates for prolonged periods or continuously:

A.  Evaporator coil iced – Defrost.

B.  Prolonged or too frequent door openings – Train staff on proper use.

C.  Excessive heat load placed in the cabinet.  Allow sufficient time for removal of heat.

D.  Dirty condenser coil- clean

E.  Controls relay failure. Technician required.

F.  Low refrigerant or other refrigeration system issue. Technician required.

7.  Noisy condensing unit: 

A.  Loose parts or mounting. Technician required.

B.  Tubing rattles - Find and increase tube clearance. Technician required.

C.  Bent fan blade causing vibration – replace blade. Technician required. 

D.  Noisy motor - May require replacement. Technician required.

8.  Unit evaporator coil excessive icing:

A.  Operating in a highly humid environment. Additional manual defrosting may be 

required.

B.  Door gasket not sealing properly. Adjust or replace gasket.

C.  Door requires adjustment. Technician required.

D.  Room ventilation or fans blowing air into the unit. Move unit, block air baffles or move 

fans.

9.  Vapor pan overfilling (water on the floor under the unit):

A.  Door being kept open to long allowing excessive ice buildup on evaporator coil. 

Review operating parameters.

B.  High room humidity causing excessive ice buildup on evaporator coil. Review 

operating parameters.

C.  Vapor pan drain plug out. Put plug back in place.

D.  Attach hose to drain pan and run into a floor drain.

10.  Control Error Messages:

“Err1” 

Sensor Failure

“Err2 

Configuration Connector Error

“Err3” 

Not Defined

“Err4” 

Under Temperature

“Err 5”  

Over Temperature

“Err6” 

Key Shorted

“Err7”  

Door Switch

“Err8”   

EPROM Possible corruption

TROUBLESHOOTING GUIDE

1.  AirScreen does not turn on (control display does not light up):

A.  Check that unit is plugged in. 

B.  Check circuit breakers and fuses.

C.  Check for damaged cord. Technician required.

D.  Control issue or other internal issue. Technician required.

2.  Closed door cabinet temperature too high (unit running):

A.  Control Setting is too high – Set a lower temperature on the control.

B.  Product temperature very warm. Give the unit time to pull product down to 

temperature.

C.  Unit may be in a defrost cycle. Wait for the defrost cycle to finish.

D.  Dirty or clogged condenser coil. Clean condenser coil.

E.  Iced up evaporator coil. Unit may require additional manual defrosting. 

F.  Refrigerant system issue. Technician required.

3.  Open door cabinet temperature to high (unit running):

A.  Control Setting is too high – Set a lower temperature on the control.

B.  Product load was not properly pre-chilled.

C.  Door left open to long.

D.  Inadequate Air Circulation – Rearrange the product load to improve air circulation. 

E.  Room ventilation or fans blowing air into the unit. Block air baffles or move fans.

F.  All 10 shelves should have trays on them. Keep empty trays in the unit.

G.  Unit may be in a defrost cycle. Wait for the defrost cycle to finish.

H.  Dirty or clogged condenser coil. Clean condenser coil.

I.  Iced up evaporator coil. Unit may require additional manual defrosting. 

J.  Review operation, installation and performance guidelines.

K.  Refrigerant system issue. Technician required.

4.  Closed door cabinet temperature to low:

A.  Control setting to low – set a higher temperature on control.

B.  Compressor running continuously (not cycling) and open displayed on control 

indicates a bad or out of adjustment door switch. Technician required.

C.  Compressor relay stuck closed. Technician required.

5.  Condensing unit fails to start- hums but trips on overload protector:

A.  Turn unit off and wait 30 minutes before turning back on to see if unit resets itself. 

B.  Low voltage should be checked by an electrician and corrected.

C.  Compressor motor Start capacitor failure.  Technician required.

D.  Condenser relay not closing or defective. Technician required.

E.  Compressor motor winding open or shorted. Technician required

F.  Internal mechanical trouble with compressor. Technician required.

SHOCK HAZARD 

NOTICE

WARNING: 

RISK OF ELECTRICAL 

SHOCK. DISCONNECT ELECTRICAL 

POWER SUPPLY BEFORE CLEANING 

ANY PARTS OF THE UNIT OR PRIOR 

TO ANY SERVICE.

SHOCK HAZARD 

NOTICE

Summary of Contents for R-AS-10

Page 1: ...REFRIGERATED AIRSCREEN SERIES OPERATING INSTRUCTIONS ASU R AS SERIES MODELS Caution Read the instructions before using the machine...

Page 2: ...tration online www fwe com warranty Scan the QR code to the right Warranty registration must be submitted within 30 days of initial delivery to be valid 4 Make sure all operators are familiar with the...

Page 3: ...livery in good order when the shipment was accepted 2 All units are factory tested for performance then carefully packaged and certified free from defects when shipped 3 Inspect the packaging for exte...

Page 4: ...Screen is extremely important for proper performance Carefully follow the guidelines listed below 1 Install unit level This is important for the health of the refrigeration system and efficient draini...

Page 5: ...Repeat the steps if necessary to get the desired temperature unit On Indicator Light Indicates the unit is turned on Cycle Indicator Light Lights when the refrigeration system is running unit is cool...

Page 6: ...s soon as possible gives more time for the unit to cool back down between open door sessions CONTINUES ON NEXT PAGE OPERATION Closed door operation When the door is closed it operates like a highly ef...

Page 7: ...be visible and should be considered a normal operating condition 5 Defrost cycles take around 15 minutes However it is advisable to allow a minimum of 45 minutes for a defrost cycle This allows time f...

Page 8: ...te corrosion of the stainless steel CONTINUED ON NEXT PAGE DEFROST CONTINUED 6 Defrost is not canceled when you open the door If possible let the defrost cycle finish and allow the compressor to come...

Page 9: ...the ingredients of cleaning solutions or disinfectants used as they may contain chlorinated solvents Always read the label of the cleaning solutions Check warnings about use on stainless steel produc...

Page 10: ...ssue or other internal issue Technician required 2 Closed door cabinet temperature too high unit running A Control Setting is too high Set a lower temperature on the control B Product temperature very...

Page 11: ...D AIRSCREEN SERIES 20 FWE Operating Instructions Refrigerated AirScreen Series WIRING DIAGRAM FWEREFRIGERATED AIRSCREEN SERIES WIRING DIAGRAMS FOR ASU 10 WIRING DIAGRAMS FOR R AS 10 R AS 10 220V R AS...

Page 12: ...g any repairs If service is required during overtime periods the difference between overtime and standard labor rates shall be paid by the purchaser Seller does not assume any responsibility for any c...

Page 13: ...rrors subject to correction All specifications subject to change without notice Printed in USA Food Warming Equipment Company Inc 5599 Highway 31W Portland TN 37148 3 IF YOU CAN DREAM IT WE CAN BUILD...

Reviews: