Section 50
00-02-0271
2018-10-23
-
16 -
K1
K2
K3
K4
K5
K6
K7
Lube
Not
Used
Motor
Cooler
Load
Alarm
SD
FAULT SHUTDOWN
Unit receives a fault at sensor #4 for instance. Motor,
Cooler, Load, Alarm and Shutdown relays are de-
energized. Postlube cycle begins. Lube Relay
energized.
LUBE CYCLE...
Postlube x:xx
On
Off
Off
Off
Off
Off
Off
Postlube expires. Lube relay de-energized. Fault is
displayed.
Low Compressor
Oil Pressure
Off
Off
Off
Off
Off
Off
Off
S1501 Mode key pressed. Shutdown type displayed.
Sensor Input #04
Class B1,Shutdown
Off
Off
Off
Off
Off
Off
Off
S1501 Reset key pressed. Unit waiting on start input.
Waiting On Start
ETM: xxxxx.x hrs
Off
Off
Off
Off
Off
On
On
NORMAL STOP (AFTER IDLE-COOLDOWN CYCLE)
Stop signal received and idle timer expired. Motor, and
Cooler relays de-energized. Postlube cycle begins.
Lube relay energized
LUBE CYCLE...
Postlube x:xx
On
Off
Off
Off
Off
On
On
Postlube cycle timer expires. The Lube relay is de-
energized. Unit returns to Waiting on Start.
Waiting On Start
ETM: xxxxx.x hrs
Off
Off
Off
Off
Off
On
On