![FW Murphy Selectronic S1501 series Installation And Operation Manual Download Page 17](http://html1.mh-extra.com/html/fw-murphy/selectronic-s1501-series/selectronic-s1501-series_installation-and-operation-manual_2352720017.webp)
Section 50
00-02-0271
2018-10-23
-
13 -
Sequence of Operations - Engine Mode
ENGINE APPLICATION
EVENT
DISPLAY
RELAY
K1
K2
K3
K4
K5
K6
K7
Lube
Crank
Ign.
Fuel
Load
Alar
m
SD
WAITING ON START
Unit monitors for a valid start signal. Shutdown and
Alarm relays are energized. * User can at this time,
press the Mode key to modify desired setup tables.
Class A inputs are scanned.
Waiting On Start
ETM: xxxxx.x hrs
Off
Off
Off
Off
Off
On
On
Start signal received. Unit advances to Prelube cycle.
Waiting On Start
ETM: xxxxx.x hrs
Off
Off
Off
On
Off
On
On
If an RPM signal is seen before the Start signal is
pressed, a fault occurs.
Unexpected
Engine Start!
Off
Off
Off
On
Off
Off
Off
PRELUBE CYCLE
Prelube cycle begins. Permissive timer starts. Lube
relay energized.
LUBE CYCLE...
Permissive x:xx
On
Off
Off
Off
Off
On
On
Permissive time expires before Permissive signal* seen
closed. Fault occurs. Lube relay is de-energized.
Permissive
Failure
Off
Off
Off
Off
Off
Off
Off
Permissive signal closed. Prelube Cycle timer started.
LUBE CYCLE...
Prelube x:xx
On
Off
Off
Off
Off
On
On
Prelube Cycle timer times down to zero. Unit advances
to Crank cycle.
LUBE CYCLE...
Prelube :00
On
Off
Off
Off
Off
On
On
CRANK CYCLE
Crank Relay energizes. If the Run Delay Preset is > 0,
the controller will wait for a Crank RPM permissive to
proceed. If set to 0, this cycle is skipped
CRANK PERMISS...
Run Delay x:xx
On
On
Off
Off
Off
On
On
Run Delay time expires before RPM > 10 is seen. Fault
occurs.
Engine Failure To
Crank!
Off
Off
Off
Off
Off
Off
Off
RPM > 10 is seen, or Crank Permissive cycle skipped.
Cranking continues with purge timer started at preset
time.
CRANK CYCLE...
Purge :xx
On
On
Off
Off
Off
On
On
Purge delay expires. Ignition relay is energized. Fuel
On delay is started.
CRANK CYCLE...
Fuel Delay :xx
On
On
On
Off
Off
On
On
Fuel On delay expires. Fuel relay energized. Crank
timer started. The Controller will monitor for a Crank
Disconnect RPM to advance to the Run Cycle.
CRANK CYCLE...
Crank :xx
On
On
On
On
Off
On
On
Crank timer expires before disconnect speed is
reached. Unit goes into Rest cycle. Crank, Ignition, and
Fuel relays are de-energized. When the Rest expires,
the Crank Cycle will repeat.
CRANK CYCLE...
Rest :xx
On
Off
Off
Off
Off
On
On
All crank attempts exhausted. Crank timer expires.
Disconnect speed not reached. Overcrank condition
occurs. All relays de-energized.
Overcrank
Shutdown!
Off
Off
Off
Off
Off
Off
Off
Summary of Contents for Selectronic S1501 series