EG Series Control Box
Display Screens and Menus
Main Control Screen
Splash Screen -The EG Series has many menu screens for
setting up the system parameters. The first to show up after
power on is the splash screen displaying system type and
version. The version and version date may change as features
and program modifications are implemented.
The Main Control Screens: This is the first screen displayed
after the 10 second start up routine is complete. The value
on the top left of the working screen is the actual value being
received by the receiver. The value on the top right side of the
working screen is the offset entered by the user.
The “No Beam Detected”- This image displays what the work-
ing screen will look like when the receiver loses the signal hit
from the laser during operation. The user entered offset is still
shown on the top right of the screen, however the actual on-
grade value is replaced on the screen by dashes.
The “Laser Receiver Bad”- EG Series has self diagnostics to
keep your system working at peak performance, if a problem
occurs the main screen will display a message for the operator.
This is the screen you will see if there is no receiver connected
to the system, or if the control box can’t communicate with the
receiver. This may indicate a disconnected receiver or problem
with the cables
Operator menu - Entered by pressing the menu button.
System Lockout Screen - When entering the menu screens,
the system lockout screen will appear. You must enter the
system password to be able to go any further into the menu
screens. If this option is not needed it may be disabled in the
installation menu.
Filtering: The filtering rate is a mathematical averaging filter
that can help to cure any jumpy behavior of the receiver. The
best setting is one place to the right of Fast for most applica-
tions
On-Grade Dead band - Is the amount of allowable on-grade
tolerance. The range is 1mm to 30mm at 1mm steps. When the
receiver is receiving the laser light in the on-grade position, the
valves will not activate until the dead band range is passed. If
the on-grade dead band is set to 10mm, the valves will not be
activated (Hydraulic Valve On) until the receiver readings are
beyond 5mm in either direction.