Page 11
Servo Motor - The EG Series valve outputs are reconfigured
to an H-Bridge style push-pull drive, capable of driving electric
actuators. This drive has a maximum current limit of 6 amps.
Refer to the wiring diagram for the proper wire connections.
Drive Cycle Time - This menu function sets how often the
output pulses are sent to the actuator called hits per- second.
The range is 1 to 15 hits per-second and unit is in milliseconds,
to calculate the hits per-second divide 1 by the milliseconds.
eg.1/0.250 = 4 hits per-second. The lower the number the
more hits per-second. For most Actuator systems starting at
100ms or 10 hits per-second is a good place to start. The fast-
er you can hit the actuator the finer the cylinder movements,
the smoother the control. The actuator response will differ
between actuator manufactures.
Push-Pull Drive - This menu function reconfigures the valve
drive to operate as a Push-Pull output. This will provide a
forward and reverse drive to the actuator.
Actuator Drive Current Limit - If there is a current limit
required for the actuator you can enable and set the current
limit required for your actuator. Most actuators on the market
today will not require current limit, you can disable the current
limit. Be aware that our drive has a max current capability of 6
amps.
*** DAMAGE TO EG SERIES CAN HAPPEN ***
*** IF THE CURRENT DRAW IS TOO LARGE ***
ServoMotor Next
Valve type
ServoMotor Setup
125ms Next
Valve cycle time
Push-Pull Next
Valve type
Disable Next
Curr.Limit 4.8A