CONTINUITY TEST

The continuity test test is only possible when batteries are installed and in good 

condition. A signal sound is audible for continuity and the LED for continuity LED 

[6] is illumitated. 

VOLTAGE TEST WITH SWITCHED LOAD, RCD TRIP TEST

 · During voltage tests, you can decrease the interference voltages from inductive 

or capacitive coupling by loading the UUT with a lower impedance than the 

tester has in normal mode. In systems with RCD circuit breakers, you can trip 

an RCD switch with the same low impedance as when you measure voltage 

between L and PE*.

 · To do an RCD trip test during voltage measurement, push the two low imped-

ance buttons [13] at the same time. If you have 10mA or 30mA RCDs between L 

and PE* in a 230V system, it will trip.

 · During load current, the low impedance LED is the indication for the flowing 

load current. This indication is not to be used for voltage test of measurement.

 · If the two pushbuttons are not used, the RCDs will not trip, even in measure-

ments between L and PE* 

 

(* Protective earth: grounding) 

 ROTARY FIELD INDICATION

The voltage testers are equipped with a double-pole rotary field indicator. The 

rotary phase indication is always active. Te symbols “R” or “L” are always displayed. 

However, the rotary direction can only be determined within a three-phase sys-

tem. Here, the instrument indicates the voltage between two external conductors.

Connect the instrument test probe with the supposed phase L2 and the handle 

test probe with the supposed phase L1. The voltage and the rotary field direction 

are dispayed. 

 · “R” signifies that the supposed phase L1 is the actual phase L1 and the sup-

posed phase L2 is the actual phase L2. 

 

 

 

 

 

 

 

 

“L” signifies that the supposed phase L1 is the actual phase L2 and the supposed 

phase L2 is the actual phase L1. 

 

 

 

 

 

 

 

When re-testing with exchanged test probes the opposite symbol has to be allu-

minated.

MEASUREMENT POINT ILLUMINATION

This voltage tester are equipped with a measurement point illumination feature. 

Thus, working under bad lighting conditions (e.g. division switch cabinets) is 

made easier. Press the button for measurement point illumination [14] to activate 

the LED flashlight.

Summary of Contents for VOLTTESTER 4.6A

Page 1: ... LED or continuity 7 LED for left rotary field 8 LED for right rotary field 9 LED for AC voltage 10 LED for positive voltage 11 LED for negative voltage 12 LED for warning voltage 13 LOW impedance switches 14 Button for measuring point illumination LED flashlight 15 AUTOTEST self check test 16 Battery case 17 Probe tip Protective cap with storage compartiments for probe tip cover and probe tip ext...

Page 2: ...e rester may no longer be used if one of several functions fail or if no fucntionality is indicated If the operator s safety cannot be guaranteed the instru ment must be removed from service and protected against use Please read the complete safety instructions in the booklet delivered with this device SAFETY ADVICES Depending on the internal impedance of the voltage detector there will be a diffe...

Page 3: ...nal usage CARRYING OUT A FUNCTION TEST When press AUTOTEST with the exception of the LED for low impedance test all LEDs should light up If the battery voltage is too low all LEDs will blink please replace the battery VOLTAGE TEST Connect both test probes with the power source As from a voltage of 6V the voltage tester switches on automatically The voltage is displayed via LEDs The different indic...

Page 4: ...ot to be used for voltage test of measurement If the two pushbuttons are not used the RCDs will not trip even in measure ments between L and PE Protective earth grounding ROTARY FIELD INDICATION The voltage testers are equipped with a double pole rotary field indicator The rotary phase indication is always active Te symbols R or L are always displayed However the rotary direction can only be deter...

Page 5: ... Replace by 2 new AAA batteries respecting the polarity Close the batterycover and re screw the screw SPECIFICATIONS LEDS LED voltage range 12V to 1000V AC DC LED resolution 12 24 50 120 230 400 690 1000V AC DC Tolerances Complies with EN 61243 3 2014 Frequency range 0 40Hz to 400Hz Response time 1 sec Auto power on 12V AC DC Voltage detection Automatic Polarity detection Full range Range detectio...

Reviews: