Chapter 2:  Installation

14

AC alarm output

The AC alarm output provides an alarm signal when the 406080A-FUR 
AC/DC Power Supply Unit cannot deliver the required power from the 
AC input. This is the case when

• No AC power is present.
• The AC fuse is blown.
• The on/off switch is in the position off.
• The output is short-circuited or heavily overloaded.
• An internal error has occurred.

To wire the 

AC alarm

 output do as follows:

1. Attach the cable to the connector marked 

AC Alarm

 according to the 

specifications in the table below:

AC ALARM (406080A-FUR AC/DC 
Power Supply Unit)

Connector type

Spring loaded terminal

Wire cross section

Up to 1.5 mm

2

Terminal 1

Closed when ok

Terminal 2

Open when ok

Terminal 3

Common

Terminal 4 

GND

Summary of Contents for 406080A-FUR

Page 1: ...AC DC POWER SUPPLY UNIT 406080A FUR OPERATOR S MANUAL www furuno com Model...

Page 2: ......

Page 3: ...rn contact your dealer about replacement The contents of this manual and equipment specifications can change without notice The example screens or illustrations shown in this manual can be different f...

Page 4: ...dard trash or at a trash site Take the used batteries to a battery collection site according to your national legislation and the Batteries Directive 2006 66 EU In the USA The Mobius loop symbol three...

Page 5: ...of any electrical equipment in such an environment constitutes a definite safety hazard KEEP AWAY FROM LIVE CIRCUITS Operating personnel must not remove equipment covers Component replacement and inte...

Page 6: ...description of the principle of operation and uses and features of the power supply Installation contains step by step guidelines how to install the power supply as a stand alone unit or in a combine...

Page 7: ...t 6 Installing 2 or 3 406080A FUR AC DC Power Supply Units 15 Chapter 3 Service and repair Support repair and service 19 Exchanging the fuses 20 Returning units for repair 21 App A Technical specifica...

Page 8: ...Table of contents vi Packing lists PL 1...

Page 9: ...of 370 W for a minimum of 2 minutes This is useful for MF HF applications and DSC transmissions of 2 minutes duration It is AC powered with a battery switch over function The 406080A FUR AC DC Power S...

Page 10: ...of input voltage range AC alarm and Short circuit protection Over temperature protection shutdown with automatic restart Switch over to battery power in case of AC supply failure No forced cooling re...

Page 11: ...DC Power Supply Unit L N GND Mains AC AC Input DC DC DC1 28 7 31 2 VDC output DC DC DC2 28 7 31 2 VDC input output Battery Battery AC LED Output LED 24 VDC Battery input GND NC Open when ok COM Commo...

Page 12: ...minals It can be used as a stand alone DC power supply or as a building block in a larger power supply When more power is needed than one power supply can give i e 300 W you can stack up to three powe...

Page 13: ...battery fuses 30 A 4 mounting bolts for mounting 1 unit M6X55 mm DIN912 Unbrako Cable relief bracket comb style 406080A FUR AC DC Power Supply Unit Installation manual this manual 2 1 1 Optional acce...

Page 14: ...wards the 406080A FUR AC DC Power Supply Unit fulfills IP32 in areas with more than 42 V and IP22 in other areas Warning Never insert or remove a power supply while its power switch is in the On posit...

Page 15: ...wing drawing shows the 406080A FUR AC DC Power Supply Unit and the position of the mounting holes It is mounted with four mounting bolts 4 mounting bolts for mounting 1 unit M6X55 mm DIN912 Unbrako To...

Page 16: ...to the wall between the wall and the 406080A FUR AC DC Power Supply Unit with four M4 x 6 mm screws 3 Fasten the 406080A FUR AC DC Power Supply Unit to the wall with 4 mounting bolts M6X55 mm DIN912 U...

Page 17: ...lid Removing the protective lid 406080A FUR AC DC Power Supply Unit To connect the cables you must remove the protective lid To do this unscrew the two screws M3x7mm Torx 8 as shown in the picture and...

Page 18: ...s 1 Remove the u shaped cut out for this input from the protective lid 2 Connect the Mains cable to the connector marked MAINS AC Mains AC Connector type Spring loaded terminal dual row connector Wire...

Page 19: ...ng mains power Use the other terminal for the mains power going to the next 406080A FUR AC DC Power Supply Unit DC output The 406080A FUR AC DC Power Supply Unit supplies a DC output To connect the DC...

Page 20: ...0A FUR AC DC Power Supply Unit Connect the cable from DC1 in 406080A FUR AC DC Power Supply Unit 1 to DC2 in 406080A FUR AC DC Power Supply Unit 2 Connect the DC cable to the connector marked DC 2 and...

Page 21: ...ery To connect the BATTERY input do as follows 1 Connect the cable to the connector marked BATTERY and the battery 2 Remove the u shaped cut out for this input from the protective lid BATTERY Connecto...

Page 22: ...f switch is in the position off The output is short circuited or heavily overloaded An internal error has occurred To wire the AC alarm output do as follows 1 Attach the cable to the connector marked...

Page 23: ...n mounted in a vertical position with the connector panel pointing downwards the unit fulfills IP32 in areas with more than 42 V and IP22 in other areas The mounting holes in the 406080A FUR AC DC Pow...

Page 24: ...16 The following drawing shows the specifications of the mounting bolts needed when installing two or three units on top of each other 2 block mount 4 x M6X100 mm DIN912 Unbrako 3 block mount 4 x M6X...

Page 25: ...of unit 1 to unit 2 2 Connect DC1 of unit 1 to DC2 of unit 2 3 For the third unit repeat steps 1 and 2 to connect unit 2 to unit 3 Caution If you need more than 3x300 W or 30 A you need to follow spec...

Page 26: ...Chapter 2 Installation 18 This page is intentionally left blank...

Page 27: ...e 3 1 1 Contact for support For support contact the distributor that supplied the 406080A FUR AC DC Power Supply Unit 3 1 2 Repair and servicing The device does not require maintenance and adjustment...

Page 28: ...is accessible from outside the housing It is positioned next to the on off switch 2 Turn the fuse holder and extract it 3 Take out the old fuse and insert a new one type 5x20 mm 6 3 AT 4 Insert and fa...

Page 29: ...tective lid 2 Pull out the fuses 3 Insert two new fuses type ATO Blade Fuse 30 A 3 3 Returning units for repair Should your FURUNO product fail please contact your dealer or installer or the nearest F...

Page 30: ...ling If the original shipping carton is not available the following general instructions should be used for repacking with commercially available material 1 Wrap the defective unit in heavy paper or p...

Page 31: ...Output power at 90 VAC 100 VAC 270 W continuous 333 W peak 2 min DC output nominal 31 2 VDC at 0 A 29 3 VDC at 10 A 28 7 VDC at 13 A AC input voltage 115 230 VAC nominal 100 240 VAC operating Alarm i...

Page 32: ...Appendix A Technical specifications 24 Survival temperature power on 40 to 80 C Dimensions H 46 5 mm L 354 mm W 265 mm Weight Approx 3 7 kg Compass safe distance 30 cm Specifications Value...

Page 33: ...ount tray option B B 1 Overview A Wall mount tray heavy duty with cable relief bracket is available and can be ordered order number 406080A opt 001 Up to 3 406080A FUR AC DC Power Supply Units can be...

Page 34: ...Appendix B Wall mount tray option 26 B 1 1 Dimensions and weight B 1 1 1 Dimensions B 1 1 2 Weight The Wall mount tray heavy duty weighs 2 5 kg...

Page 35: ...than 3 406080A FUR AC DC Power Supply Units C 1 Wiring 4 or more 406080A FUR AC DC Power Supply Units Important You must connect the units as shown in the drawing This is to make sure that a single co...

Page 36: ...Appendix C Special installation 28 This page is intentionally left blank...

Page 37: ...29 Appendix D Declaration of conformity D D 1 OEM declaration...

Page 38: ...Appendix D Declaration of conformity 30 D 2 CE LVD EMC The 406080A FUR AC DC Power Supply Unit is CE certified LVD EMC directives as stated in the Declaration of Conformity with LVD and EMC Directives...

Page 39: ...85 1 0 2 8 7 1 6 5 37 21 2 4 7 8 81 7 32 5 6833 81 7 85 167 7 21 0 7 5 6 7 6 5 686 6 7 33 1 6 5 686 6 7 33 1 6 5 686 5 5 7 3 67 3 77 21 2 7 0 686 2 80 17 352 8 7 21 57 7 23 5 725 6 0 18 20 PL 1...

Page 40: ...7KH SDSHU XVHG LQ WKLV PDQXDO LV HOHPHQWDO FKORULQH IUHH 85812 XWKRUL HG LVWULEXWRU HDOHU VKLKDUD FKR 1LVKLQRPL D 3 1 6 3 3ULQWHG LQ DSDQ OO ULJKWV UHVHUYHG 2 7 3XE 1R 20 7 85...

Reviews: