RELAY DE-ACTIVATION PROCEDURES FOR GS2-200 UNITS 

 

CAUTION 

 

DO NOT WORK ON PANEL WITH POWER APPLIED! 

 
 
 

1.  Disconnect all power sources from GS2-200 unit. 

2.  Remove the 8 screws securing the bottom panel and gently pry bottom panel loose. 

3.  Locate relay activation switch on the rear of the control panel as shown in Figure 1. 

4.  Flip the Relay Activation Switch to the “OFF” position as indicated in Figure 2. 

5.  Reinstall bottom panel using the 8 screws removed in step 3. 

6.  Apply incoming power to the unit  by  connecting the power cord and turning the power switch located near 

the power cord on.  Make sure the blower is not running and the green power light is off.  This is called the 

“Soft On” state.  

7.  Now that the physical switch is activated and the  unit is in the “Soft On” state, the software will need to be 

reprogramed via a flash drive with a configuration file and the USB port on the control board. (Contact Fumex 

to acquire the correct configuration file for your unit). 

8.  Reprogram the software  by  changing  the  “remoteSwitchOnly”  setting in the configuration file  to  “0”.  This 

will  unlock  the  Control Board power button.    The  ON/OFF function will only  be able to be controlled  by the 

front panel on the unit.  

9.  After changing and  saving  the configuration  file, plug the flash drive into the USB port  on the front of the 

control board.  (Make sure the unit is in the “Soft On” state before plugging in the flash drive.)  

10.  After the reprogramming is complete the light above the USB port will turn green and remain lit until the flash 

drive is removed from the USB port. 

11.  Remove the flash drive and start the unit as described in the “Controls” section. 

 
 
 
 

Once the relay activation switch is turned off and the configuration file has been 
reprogrammed the unit will only start by using the front control panel. All relays 
will become non-functional.     

 

 

 

 

 

 

 

Summary of Contents for GS2-200

Page 1: ...any solid state speed control device WARNING For general ventilating use only Do not use to exhaust hazardous or explosive materials or vapors WARNING Use only a 10 Amp fuse CAUTION Do not operate wit...

Page 2: ...o c a t i n g t h e a i r c l e a n e r Placing the GS2 200 unit as close as possible to the pollution source reduces the amount of ducting needed reduces back pressure lowers power consumption and im...

Page 3: ...Filter and then press the FILTER RESET button If the light remains illuminated or turns off and comes back on then contact Fumex for assistance The GS2 200 unit contains a VOC sensor to detect odors...

Page 4: ...s commonly found in industrial manufacturing processes Part FX4 Blend of FX1 with FX2 for broad spectrum gas treatment SELECTING GAS ODOR ADSORBENT FILTERS Media Selection and Service Life Fumex offer...

Page 5: ...tions only 10 Amp fuse and check the product If the replacement fuse blows a short circuit may be present and the product should be discarded or returned to an authorized service facility for examinat...

Page 6: ...returned PREPAID to Fumex LLC 1150 Cobb International Pl Kennesaw GA 30152 There are no warranties which extend beyond the descriptions set forth in this warranty notwithstanding any knowledge of Fume...

Page 7: ...flash drive with a configuration file and the USB port on the control board Contact Fumex to acquire the correct configuration file for your unit 8 Reprogram the software by changing the remoteSwitchO...

Page 8: ...ia a flash drive with a configuration file and the USB port on the control board Contact Fumex to acquire the correct configuration file for your unit 8 Reprogram the software by changing the remoteSw...

Page 9: ...9 DRAWINGS AND FIGURES Figure 1...

Page 10: ...10 DRAWINGS AND FIGURES Figure 2 Figure 3 ON OFF Relay Activation Switch...

Reviews: