In case of a disconnected sensor or temperature out specified range a will appear on the display.
Process stages:
Initial delay (delay to start the control)
Fan-delay (delay to fan return)
Refrigeration
Pre-defrost
Defrost
Draining
Hour meter display: Number of hours worked by the compressor
NOTE:
If the number of hours of the compressor exceeds 999, the number will be shown in two steps:
Thousands first and then hundreds, tens and units.
6.2 - Manual defrost (instant)
To perform a manual defrost regardless of programming, keep the key pressed for 4 seconds until
the indication is shown. Release the key and will appear.
If the instrument is in the defrost cycle and an interruption is required, proceed as per the instructions
above until the indication is shown. Release the key and will appear.
6.3 - Minimum and maximum temperature register
By pressing , short touch, the sign will appear and the maximum and minimum temperatures
of the sensor S1(ambient temperature) will appear. Soon will appear showing the minimum and
maximum temperatures of the sensor S2 (evaporator). Next will appear the minimum and maximum
voltages, preceded by the sign .
Note:
To reset settings, hold the key through all the minimum and maximum temperature
visualization until appear.
6.4 - Visualizing the current weekday and time
Press quickly the key. It will appear:
DAY OF THE MONTH MONTH YEAR HOURS MINUTES SECONDS DAY
OF THE WEEK
6.5 - Viewing the supply voltage
By pressing the and keys for 5 seconds, it will appear the supply voltage of the instrument,
preceded by the message.
SET
SET
- Indication of high voltage
- Indication of low voltage
- Reference to the memory of the datalogger
- Indication to clear the memory of the datalogger
- Indicates that the instrument is resetting the values
Frontal LEDs
COMP - refrig / compressor (16A)
FANS - evaporator fans (5A)
DEFR - defrost (1A)
ALRM - alarm (5A)
ECO - economic setpoint active (saving energy)
CO
MP
- The sensor S1 (black) must be in the ambient.
- The sensor S2 (gray) must be placed in the
evaporator through metallic cramp.
- The sensor cable length can be increased by the
user until 200 meters using the PP 2 x 24 AWG
cable.
Power
supply
0 +12Vdc +24Vdc
AL
RM
DE
FR
FA
NS
Loads
supply
CO
MU
M
S
en
so
r S
1
(b
la
ck
)
S
en
so
r S
2
(g
ra
y)
4
5
6
7
8
9 10 11 12
3
2
1
2
1
4 - 5
4 - 6
12Vdc
24Vdc
9 - WIRING DIAGRAM
Compressor
supply
Serial communication
RS-485
Selection for monitoring
the voltage
Digital
input 1
Digital
input 2
12V
B A
24V
COMP: 12(8)A / 240 Vac 1HP
FANS: 5(3)A / 240Vac 1/8HP
DEFR: 1(3)A / 240Vac
ALARM: 5(3)A / 240Vac 1/8HP
FAN-DELAY
REFRIGERATION
DEFROST
DRAINING
Indication released
F09
to
F10
F21 F51
to to
F30 F56
F31
F11
to
F20
Indication locked if enabled in
(
F30)
PRE-DEFROST
F24
6.7 - Manual datalogger activation
Press and simultaneously for 10 seconds to activate or deactivate the operation of the internal
voltage recorder (data-logger). The message will be showned followed by the message
when the data-logger is activated and when it is deactivated.
Note: The status of the datalogger will only change alternate between and if the function
F46 is set to 2 (manual datalogger operation).
6.8 - Hour-meter reset
When the number of hours with the compressor on reaches the value set in F63, the display will show a
warning, indicating that maintenance should be done. To reset this counter (It can be done only
after the warning occurs), press for 10 seconds.
6.9 - Turn off the control functions
Pressing for 5 seconds, the controller will go to a state where only temperatures and voltages are
read, where no control are performed and where all outputs kept off. Communication with SITRAD
software and the Datalogger will still work. To make the device fully operational again, press again
for 5 seconds.
SET
TC-960Ri LOG
RS-485
®
A
A
B
B
A B
A
A
B
B
A B
RS-485
7 - UNIT SELECTION (°C / °F)
To define the unit that the system will use to operate, enter into the functions menu using the
access code “231” and confirm it by hitting key . Press the key. It will appear , press again
to enter the function. Use the or keys
to choose between or and confirm
with the key. After selecting the unit the message will appear, and the instrument will return
to the function . Whenever the unit is altered, the parameters should be reconfigured, since they
assume ”standard” values.
8 - INDICATORS AND ALARMS
- Low temperature
- High temperature
- Voltage out of range
- Open door
- Pressostat
- Datalogger memory full
- Economic setpoint active
- Outputs manually deactivated
- Compressor maintenance
- Compressor ON without reaching the setpoint (F20)
- Ambient sensor S1 disconnected or temperature out of range
- Evaporator sensor S2 disconnected or temperature out of range
- Temperature Indication
- Indication that defrost will be performed
- Indication of activation
- Indication of deactivation
6.6 - Clearing datalogger memory:
Press the and keys for 4 seconds to display . The display shows . If you
don't want to clear the memory press . To clear the memory press until is displayed and
press to confirm and exit the function.
SET
SET
SET
SET
SET
SET
Over the specifield current
use a contactor.
Brown - A
Red - B
Serial
communication
RS-485
External
mesh
terminal
grounded
Serial interface
RS-485
Full Gauge
RS-485 Serial Interface
®
Device used to establish the
connection Full Gauge Controls’
instruments with the Sitrad
.
Distribution Box
Used to connect more than one instrument to the Interface. The
wire's connections must be made in agreement with the following
rules: terminal
A
of the instrument connects to the terminal
A
of
the distribution box, that must be connected with the terminal
A
of
the Interface. Repeat the action for terminals
B
and
, being
the cable shield.
the terminal of distribution box must be connected to the
respective terminals of each instrument.
IMPORTANT
As chapters of IEC 60 364 norms:
1:
Install protectors against over voltage on power supply
2:
Sensor cables and computer signals can be together, however not at the same place where power supply
And load drive pass for.
3:
Install suppresor of transient (RC filter) in parallel to loads, as for to increase the useful life of the relays.
10 - INTEGRATING CONTROLLERS, RS-485 SERIAL INTERFACE
AND COMPUTER
ENVIRONMENTAL INFORMATION
Package:
The packages material are 100% recyclable. Just dispose it through specialized
recyclers.
Products:
The electro components of Full Gauge controllers can be recycled or reused if it is
disassembled for specialized companies.
Disposal:
Do not burn or throw in domestic garbage the controllers which have reached the end-of-
life. Observe the respectively law in your region concerning the environmental
responsible manner of dispose its devices. In case of any doubts, contact Full Gauge
controls for assistance.