background image

F27 - Evaporator temperature (S2) determine the end of defrost

If  evaporator  temperature  (sensor  S2)  reaches  the  adjusted  value,  the  end  defrost  will  happen  for 
temperature. With this , the defrost process is optimized.

F28 - Maximum defrost duration (for security)

This function serves to adjust the maximum value of time to defrost. If in this period the evaporator 
temperature will not reach the configured value in F27 a point will be blinking on inferior down right side of 
display indicating that the end defrost ocurred for time and not for temperature.
This can happen when the adjusted temperature is very high, the limit time will be not enough, the S2 
sensor is detached or not in contact with the evaporator.

F29 - Fan turned on during defrost

It possibilities the fan functioning during defrost.

Example:

 Natural defrost or by finned resistances installed outside the evaporator.

F30 - Temperature indication (S1) locked during defrosting

This function is aimed at avoiding a rise in the ambient temperature due to the defrost cycle. The last 
temperature measured in the refrigeration cycle will be frozen in the display during the defrost cycle. The 
indication will be un-frozen when the process returns to the refrigeration cycle.
Note: The value entered in F28 cannot be zero.

F31 - Draining time (dripping of defrost water)

Necessary time for dripping, it means, to drain the last water drops of the evaporator. All the outputs keep 
turned off. If you do not need this stage, adjust this time for ”zero”.

F32 - Low ambient temperature alarm

If the ambient temperature (S1 sensor) falls below the point set here during the refrigeration cycle it will be 
indicated in the display by the message             and the alarm output will be activated.

F33 - Low temperature alarm hysteresis

This value is the temperature difference required to turn off the low ambient temperature alarm output.

F34 - High ambient temperature alarm

If the ambient temperature (S1 sensor) reaches the point set here during the refrigeration cycle it will be 
indicated in the display by the message            and the alarm output will be activated.

F35 - High ambient temperature alarm hysteresis

This is the temperature difference required to turn off the high ambient temperature alarm output.

F36 - Alarm inhibition time after powering the instrument on

During this period of time, the high or low temperature alarm is kept off waiting for the system to start 
working mode. If the voltage is out-of-range or the condition in F20 occurs, the indication will be shown in 
the display but the relay will only be triggered after the time set in this function.

F37 - Alarm inhibition time after draining

This function works to inhibit the alarm for some time due to an occasional temperature rise caused by the 
defrost cycle. The alarm is disabled during defrosting and draining operations.

F38 - Inhibition time for the open door alarm (only buzzer)

During this time, the open door alarm is kept off (see also F41).

F39 - Alarm time (on cycle)

This is the period for which the alarm output will stay on. The alarm will sound for the following reasons: 
High  or  low  temperature  (F32  and  F34),  when  the  voltage  is  out-of-range  (F42  and  F43),  and  if  the 
compressor is on without reaching the setpoint (F20).

F40 - Alarm time (off cycle)

This is the period for which the alarm output will stay off.

F41 - Buzzer enabling 

Enable or disable the activation of the buzzer. This will sound when either of the two digital inputs is set to 
“open door signaling", and the event has been detected.

F42 - Minimum supply voltage (protection)

F43 - Maximum supply voltage (protection)

Maximum and minimum thresholds for the instrument's supply voltage aiming at protecting the outputs. If 
the voltage is out of this range, the outputs are turned off.
Note: The selector jumper for the supply voltage must be properly positioned to select between 12 and 24V, 
as per the connection diagram shown in item 7 of this manual.

F44 - Offset voltage indication

This parameter lets you adjust the offset voltage indication. 

F45 - Time to validate the voltage reading

This is the time that the instrument waits before indication an under- or over-voltage after verifying that the 
voltage is out of the range set in F42 and F43.

F46 - Datalogger operation mode  (***)

Allows to choose between the following operation modes of the datalogger:

0 - Always Off
1 - Always On
2 - Manual 

F47 - Sampling time (time between records in the memory)

This is the time in seconds that the controller records samples of the temperature information, the output 
state and the digital input state.

F48 - Minimum temperature change to force writing data to the memory

This is the temperature difference in relation to the last data written in the datalogger so that the data written 
in the memory are recorded regardless of the sampling time set in F47. Disabled if zero.

F49 - Variation of the outputs to force data recording:

F50 - Overwrite old records when memory is full?

This function indicates whether the controller should start writing the new data at the beginning of the 
datalogger's memory when it is full.  This prevents that the latest data recorded from equipment be erased 
first. If set to zero, when the data-logger memory is full the instrument and Sitrad will signal full memory.

F51 - Number of defrosts per day (Monday to Friday)

The defrost cycles are evenly distributed in accordance with the number of defrosts set per day, always 
considering the preferred time. The value can be adjusted to 1, 2, 3, 4, 6, 8 or 12. This function works to 
schedule the operation from Monday to Friday

Indicates whether the change in any output will force the recording of data in memory regardless of the time 
of sampling set in F47:

 

F52 - Preferred time to start defrosting (Monday to Friday)

This must be set to the preferred time (reference time) for the daily defrost to be performed. This function 
works to set the time from Monday to Friday.
Example: If the preferred time is set to 1 PM (and the number of defrost cycles is set to 4 and the interval is 
6 hours), defrosting will be performed at 1 AM, 7 AM, 1 PM and 7 PM on the same day. In the example, the 
suggested day is Monday. The idea, however, works for all weekdays.

                      

                                
                                                    

F53 - Number of defrosts per day (Saturday)

The defrost cycles are evenly distributed in accordance with the number of defrosts set per day, always 
considering the preferred time. The value can be adjusted to 1, 2, 3, 4, 6, 8 or 12. This function works to 
schedule the operation for Saturdays.

F54 -

 

Preferred time to start defrosting (Saturday)

This must be set to the preferred time (reference time) for the daily defrost to be performed. This function 
works to set the time for Saturday.

F55 -

 

Number of defrosts per day

 

(Sunday)

The defrost cycles are evenly distributed in accordance with the number of defrosts set per day, always 
considering the preferred time. The value can be adjusted to 1, 2, 3, 4, 6, 8 or 12. This function works to 
schedule the operation for Sundays.

F56 -

 

Preferred time to start defrosting (Sunday)

This must be set to the preferred time (reference time) for the daily defrost to be performed. This function 
works to set the time for Sunday.

F57 - Time to start the economy setpoint (Monday to Friday)

This is the time for which the setpoint assumed for process control becomes the economy setpoint 
adjusted in accordance with item 4.1 of this manual.
This function works to set the time from Monday to Friday.

F58 - Duration of the economy setpoint (Monday to Friday)

This is the time (in hours) that the assumed setpoint will be the "economy setpoint" for the week days 
from Monday to Friday starting from the time set in F57.

F59 -

 

Time to start the economy setpoint (Saturday)

This is the time for which the setpoint assumed for process control becomes the economy setpoint 
adjusted in accordance with item 4.1 of this manual.
This function works to set the time for Saturday.

F60 -

 

Duration of the economy setpoint (Saturday)

This is the time (in hours) that the assumed setpoint will be the "economy setpoint" for Saturdays starting 
from the time set in F59.

F61 -

 

Time to start the economy setpoint (Sunday)

This is the time for which the setpoint assumed for process control becomes the economy setpoint 
adjusted in accordance with item 4.1 of this manual.
This function works to set the time for Sunday.

F62 -

 

Duration of the economy setpoint (Sunday)

This is the time (in hours) that the assumed setpoint will be the "economy setpoint" for Sundays starting 
from the time set in F61.

F63 - Tempo máximo de operação da saída COMP p/ manutenção

Whenever the COMP output is activated the instrument will count its operating time. When the time 
counted is equal or higher than the time set in this function, the display will show the message          , 
meaning that the compressor must be serviced.
Note: The value adjusted in this parameter will be multiplied by ten.
Example: Value adjusted = 1, then 1x10 = 10 hours for the next service.

F64 - Intensity of the digital filter applied to sensor S1

This filter aims at simulating an increase of environment sensor mass, thus increasing its response time 
(thermal inertia). The larger the value adjusted in this function, the longer the response time of the 
sensor.
A typical application requiring this filter is the freezer for ice cream or frozen goods, because when the 
door is opened a hot air mass directly reaches the sensor, causing a quick rise in the indication of the 
measured temperature, thus causing the compressor to be activated unnecessarily many times.

F65 -

 

Preferred viewing mode (****)

In this parameter the user configures which viewing mode of quantities the display will work, it can be set 
between:

0 - ambient temperature

1 - supply voltage
2 - temperature / voltage (alternately)

F66 - Network equipment address RS - 485 

Equipment's network address for communicating with Sitrad  software.
Note: A network must not have different equipments with the same address.

®

13:00

07:00

19:00

01:00

Defrost

Defrost

Defrost

Defrost

Monday

5 - SEETING CURRENT TIME AND THE DAY FOR THE WEEK

Inside the function menu, press the         key until the message           appear on the display. 
Tap the           key. The settings will appear in the following order:

      

HOURS      MINUTES      DAY OF THE WEEK

Ex: 12:43 - Friday

Hours
Minutes
Day of the week

                                

6 - FACILITATED ACCESS

6.1 - Process stage, elapsed time and evaporator temperature 

(S2) and hour-meter

Press         , with a short touch, and the process step and the time elapsed (in minutes) in this process 
will be shown. Then the evaporator temperature (S2) and the number of hours of the compressor (for 
maintenance control) will also be shown.

SET

Summary of Contents for TC-960Ri LOG

Page 1: ...g fan delay Minimum time of compressor turned on Minimum time of compressor turned off Compressor status with inoperative ambient temperature sensor S1 Fan on with compressor off refrigeration Fan stopped for high temperature in the evaporator S2 Fan return hysteresis after stopping due to high evaporator temperature Maximum refrigeration time for security if F22 1 Evaporator temperature to start ...

Page 2: ... that the compressor will keep turned off it means the time period between the last stopped and the next started It serves to alliviate the pressure and to increase the useful life of the compressor F13 Compressorstatuswithdetachedambientsensor S1 If the ambient sensor S1 is detached or out specified range the compressor assumes the configured statusinthisfunction Exemple For counters that storage...

Page 3: ...emoryisfulltheinstrumentandSitradwillsignalfullmemory F51 Numberofdefrostsperday MondaytoFriday The defrost cycles are evenly distributed in accordance with the number of defrosts set per day always considering the preferred time The value can be adjusted to 1 2 3 4 6 8 or 12 This function works to scheduletheoperationfromMondaytoFriday Indicateswhetherthechangeinanyoutputwillforcetherecordingofda...

Page 4: ...hat maintenance should be done To reset this counter It can be done only afterthewarningoccurs press for10seconds 6 9 Turn off the control functions Pressing for 5 seconds the controller will go to a state where only temperatures and voltages are read where no control are performed and where all outputs kept off Communication with SITRAD softwareandtheDataloggerwillstillwork Tomakethedevicefullyop...

Page 5: ...or PROTECTIVE VINYL This adhesive vinyl included inside the packing protects the instruments against water drippings as in commercial refrigerators for example Do the application after finishingtheelectricalconnections Remove the protective paper and apply the vinyl on the entire superior part of the device folding the flaps as indicated by thearrows 72 mm Dimension of the clipping for setting of ...

Reviews: