MECHANICAL DATA
ELECTRICAL DATA
Project_______________________Type______________Model #___________
Remarks__________________________________________________________
T8
T5
This Ballast Will Operate Following Lamps.
1 X F21T5, F28T5, F32T8, F40T12 (34W), 32WCRT9, 22W CRT5, FB32T8, FB34T12
BALLAST TYPE / OUTPUT TYPE
EMERGENCY
INPUT VOLTAGE
120V OR 277V
10%, 60 Hz
+
AC INPUT POWER RATING
2.7W
AC INPUT CURRENT RATING
130mA
BATTERY TYPE
MAINTENANCE FREE - HIGH TEMPERATURE RECHARGEABLE SEALED NI-CAD
BATTERY VOLTAGE
3.6Vdc
BATTERY CHARGING CURRENT
110mA
BATTERY RATING
9.0Wh
BATTERY CAPACITY
2.5Ah
TEMPERATURE RATING (AMBIENT)
0°C TO 50°C (32°F TO 122°F)
MAX INITIAL LIGHT OUTPUT
500 LUMENS
MINIMUM ILLUMINATION TIME
90 MINUTES
RECHARGE TIME
24 HOURS
TEST SWITCH TYPE
ILLUMINATED TEST SWITCH PILOT LIGHT
CHARGING INDICATOR LIGHT TYPE
LED
CASE PROFILE
14.17”L X 1.22”W X 1.14”H X 13.67” MOUNTING CENTER
CASE WEIGHT
1.8 lbs.
CASE TYPE
VANDAL RESISTANT - SEALED
CASE CONTRUCTION
GALVANIZED STEEL
WIRE CONNECTION
STANDARD WIRE LEADS
APPROVAL CLASS
UL - LISTED FOR DAMP LOCATION - FACTORY OR FIELD INSTALLATION
CODE COMPLIANCE
MEETS OR EXCEEDS UL924 - N.E.C AND NFPA 101 LIFE SAFETY CODE EMERGENCY OPERATING REQUIREMENT
AC COMPATIBILITY
ELECTRONIC FLUORESCENT - STANDARD AND DIMMING
LAMP COMPATIBILITY
FLUORESCENT SINGLE / BI-PIN / 4-PIN WITHOUT INTEGRAL STARTER
LUMINAIRE COMPATIBILITY
INDOOR SWITCHED AND UN-SWITCHED
END OF LIFE (EOL) COMPATIBILITY
YES (TIME DELAY CIRCUIT)
WARRANTY
5 YEARS
Input
Output
Wire Color
Wire Length Wire Color Wire Length
Black
45.0”
Blue
45.0”
Black/White
37.0”
Blue/White
45.0”
White
45.0”
Yellow
45.0”
Orange
45.0”
Red
45.0”
Connector
Red/White
45.0”
White
28.0”
Violet
45.0”
White
28.0”
Brown
45.0”
Ni-Cd
DAMP
WIRE LENGTH (Inches)
SPECIFICATION SHEET:
FH10-DUAL-500L
TOP VIEW
SIDE VIEW
1/17
Fulham Co. Inc. Address : 12705 South Van Ness Ave., Hawthorne, CA 90250 Tel.: 1-323-779-2980, Fax.: 1-323-754-9060. Website: www.fulham.com
Description:
Firehorse Emergency Ballast for use with or without AC ballast designed to add emergency lighting when main AC power
is interrupted for minimum of 90 minutes at reduced illumination. The emergency ballast is not intended for general purpose lighting applications.
Complies with minimum light output for emergency lighting equipment as per UL 924, supplement “SH”. Consult with factory when using EM
Ballast with low mercury lamps (TCP).
2006-132-1 Rev J