MECHANICAL DATA

ELECTRICAL DATA

Project_______________________Type______________Model #___________

Remarks__________________________________________________________

T8

T5

This Ballast Will Operate Following Lamps.

1 X F21T5, F28T5, F32T8, F40T12 (34W), 32WCRT9, 22W CRT5, FB32T8, FB34T12

BALLAST TYPE / OUTPUT TYPE

EMERGENCY

INPUT VOLTAGE

120V OR 277V

10%, 60 Hz

+

AC INPUT POWER RATING

2.7W

AC INPUT CURRENT RATING

130mA

BATTERY TYPE

MAINTENANCE FREE - HIGH TEMPERATURE RECHARGEABLE SEALED NI-CAD

BATTERY VOLTAGE

3.6Vdc

BATTERY CHARGING CURRENT

110mA

BATTERY RATING

9.0Wh

BATTERY CAPACITY

2.5Ah

TEMPERATURE RATING (AMBIENT)

0°C TO 50°C (32°F TO 122°F)

MAX INITIAL LIGHT OUTPUT

500 LUMENS

MINIMUM ILLUMINATION TIME

90 MINUTES

RECHARGE TIME

24 HOURS

TEST SWITCH TYPE

ILLUMINATED TEST SWITCH PILOT LIGHT

CHARGING INDICATOR LIGHT TYPE

LED

CASE PROFILE

14.17”L X 1.22”W X 1.14”H X 13.67” MOUNTING CENTER

CASE WEIGHT

1.8 lbs.

CASE TYPE

VANDAL RESISTANT - SEALED

CASE CONTRUCTION

GALVANIZED STEEL

WIRE CONNECTION

STANDARD WIRE LEADS

APPROVAL CLASS

UL - LISTED FOR DAMP LOCATION - FACTORY OR FIELD INSTALLATION

CODE COMPLIANCE

MEETS OR EXCEEDS UL924 - N.E.C AND NFPA 101 LIFE SAFETY CODE EMERGENCY OPERATING REQUIREMENT

AC COMPATIBILITY

ELECTRONIC FLUORESCENT - STANDARD AND DIMMING

LAMP COMPATIBILITY

FLUORESCENT SINGLE /  BI-PIN / 4-PIN WITHOUT INTEGRAL STARTER

LUMINAIRE COMPATIBILITY

INDOOR SWITCHED AND UN-SWITCHED

END OF LIFE (EOL) COMPATIBILITY

YES (TIME DELAY CIRCUIT)

WARRANTY

5 YEARS

Input

Output

Wire Color

Wire Length Wire Color Wire Length

Black

45.0”

Blue

45.0”

Black/White

37.0”

Blue/White

45.0”

White

45.0”

Yellow

45.0”

Orange

45.0”

Red

45.0”

Connector

Red/White

45.0”

White

28.0”

Violet

45.0”

White

28.0”

Brown

45.0”

Ni-Cd

DAMP

WIRE LENGTH (Inches)

SPECIFICATION SHEET:

FH10-DUAL-500L

TOP VIEW

SIDE VIEW

1/17

Fulham Co. Inc. Address : 12705 South Van Ness Ave., Hawthorne, CA 90250 Tel.: 1-323-779-2980, Fax.: 1-323-754-9060. Website: www.fulham.com

Description:

Firehorse Emergency Ballast for use with or without AC ballast designed to add emergency lighting when main AC power

is interrupted for minimum of 90 minutes at reduced illumination. The emergency ballast is not intended for general purpose lighting applications.
Complies with minimum light output for emergency lighting equipment as per UL 924, supplement “SH”. Consult with factory when using EM
Ballast with low mercury lamps (TCP).

2006-132-1 Rev J