Heat Pump, Split System, Single Service, 3 phase
Maintenance Document
1394-1
23
4 Faults
4.1 Fault
List
4.1.1 Hydraulic Unit Fault
Faults which occur on the Hydraulic Unit are shown
by the symbol . Press the info key for details on the
cause of the fault. The following information is
displayed:
•
Description of the error
•
Location of the error (sensor or contact)
•
Reset. Depending on its type, the fault can be
manually or automatically deleted:
Manual delete: the text displayed when pressing
the info key shows "reset ?". Press OK once, the
yes flashes; press again to confirm deletion of the
fault.
Faults whose deletion is automatic are
automatically reset.
•
Heat pump op: shows whether or not the heat pump
operates despite the fault.
Reset
No.: Designation of error
Location
(connection)
Manual
Auto
HP op
10: Outdoor sensor
B9
No
No
Yes
33: Heat pump flow temp sensor error
B21
No
No
Yes
44: Heat pump return temp sensor error
B71
No
No
per diagram
50: DHW temp sensor
B3
No
No
Yes
60: Room sensor 1
No
No
Yes
65: Room sensor 2
No
No
Yes
105: Maintenance message
No
No
Yes
121: HC1 flow temp not reached
No
No
Yes
122: HC2 flow temp not reached
No
No
Yes
127: Legionella protection temp not reached
No
No
Yes
369: External fault (safety component)
No
370: Outdoor unit fault*
Yes
Yes
No
* A fault in the outdoor unit is indicated by LED located on the Hydraulic Unit interface board.
LED display
LED 2 (green)
LED 1(red)
Fault description
1 Flash
1 Flash
Communication error between Hydraulic Unit and Outdoor unit.
4 Flashes
1 Flash
Heat pump capacity signal error (Open or short).
4 Flashes
2 Flashes
Hydraulic Unit heat-exchange thermistor Error.
6 Flashes
3 Flashes
Inverter error.
6 Flashes
4 Flashes
Active filter error.
PFC error.
7 Flashes
1 Flash
Discharge thermistor error.
7 Flashes
2 Flashes
Compressor thermistor error.
7 Flashes
3 Flashes
Heat-exchange thermistor (outlet) error.
Heat-exchange thermistor (intermediate) error.
7 Flashes
4 Flashes
Outdoor thermistor error.
7 Flashes
7 Flashes
Heat sink thermistor (inverter) error.
Heat sink thermistor (P.F.C.) error.
7 Flashes
8 Flashes
Expansion valve thermistor error.
8 Flashes
4 Flashes
Current sensor error.
8 Flashes
6 Flashes
Pressure sensor error.
Pressure switch error.
9 Flashes
4 Flashes
Current trip.
9 Flashes
5 Flashes
Detection of compressor position error.
Compressor start up error.
9 Flashes
7 Flashes
Outdoor unit fan motor error.
10 Flashes
1 Flash
Discharge temperature protection.
10 Flashes
3 Flashes
Compressor temperature protection.
10 Flashes
5 Flashes
Low pressure abnormal.
Continuous flashing (1 sec ON / 1 sec OFF)
Pump down operation.