Heat Pump, Split System, Single Service, 3 phase
102
Maintenance
Document
1394-1
DHW stor tank since maint (7091):
The time elapsed (in months) since the last
maintenance. If the value is greater than the setting
"DHW tank interval" (Line 7090), this symbol will be
displayed and a maintenance message will appear in
the Info section:
11: TWW DHW tank period (Priority 6)
Emergency mode
If the heat pump is not operating properly, a
emergency service can be maintained. The
emergency mode enables the installation to be run
with the available heaters (flow, storage tank, DHW
tank). In this case the compressor will remain off.
Line no.
Programming line
7141 Emergency
operation
7142
Emergency operation function type
Emergency operation (7141):
Emergency operation can be activated and
deactivated manually.
•
Off:
Emergency operation is deactivated.
•
On:
Emergency operation is activated.
Emergency operation function type (7142):
•
Manual:
Emergency operation can be activated/deactivated
only through the Emergency operation setting on line
7141.
•
Automatic:
As soon as a fault occurs on the heat pump,
emergency operation is automatically switched on. It
stops when the fault is removed and, if necessary,
cleared (reset). Emergency mode may however be
activated / deactivated manually via the "Emergency
operation" setting on line 7141.
Simulation
Line no.
Programming line
7150
Simulation outside temp
Simulation outside temp (7150):
To make the starting-up and troubleshooting
processes easier, it is possible to simulate an outdoor
temperature in the range of -50...+50°C. During
simulation, the current, composite and attenuated
outdoor temperatures are ignored and substituted
with the adjusted simulation temperature.
Computation of the three outdoor temperatures
based on the actual outdoor temperature continues to
be performed during the simulation, and these
temperatures are available again when the simulation
is over.
This function can be deactivated by selecting -.- on
this line or automatically, after a 5 hour waiting
period.
Person in charge
Line no.
Programming line
7181, 7183
Telephone number of person in charge
These lines are used to specify the telephone
numbers associated with the corresponding alarms.