En-7

7) Heater room temperature correction

Depending on the installed environment, the room temperature sensor 
may require a correction.  
The settings may be changed as shown in the table below.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

Standard

31

00

Lower control

01

Slightly warmer control

02

Warmer control

03

8) Auto restart

Enable or disable automatic system restart after a power outage. 

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

Yes

40

00

No

01

*  Auto restart is an emergency function such as for power failure etc.  

Do not start and stop the indoor unit by this function in normal operation.  
Be sure to operate by the control unit, or external input device.

9)  Indoor room temperature sensor switching function

(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote 
controller temperature sensor. 

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

No

42

00

Yes

01

*  If setting value is “00” : 

 Room temperature is controlled by the indoor unit temperature sensor.

*  If setting value is “01” :

Room temperature is controlled by either indoor unit temperature sensor 
or remote controller unit sensor.

10) Remote controller signal code

Change the indoor unit Signal Code, depending on the remote controllers.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

A

44

00

B

01

C

02

D

03

11) External input control

“Operation/Stop” mode or “Forced stop” mode can be elected.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

Operation/Stop mode

46

00

(Setting forbidden)

01

Forced stop mode

02

12) Room temperature control switching

(Only for Wired remote controller)
This setting is used to set the room temperature control method when the 
wired remote controller is selected by the Indoor room temperature sensor 
switching function.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

Control by the sensors of 
both the indoor unit and the 
wired remote controller.

48

00

Control only by the sensor of 
the wired remote controller

01

13) Setting record

Record any changes to the settings in the following table.

Setting Description 

Setting Value

Filter sign

Ceiling height

Outlet directions

Embedding the indoor unit 
in a wall

Static pressure

Cooler room temperature 
correction
Heater room temperature 
correction

Auto restart

Indoor room temperature 
sensor switching function

Remote controller signal code

External input control

Room temperature control 
switching

After completing the FUNCTION SETTING, be sure to turn off the power 
and turn it on again.

10. TEST OPERATION

(1)  If the operation lamp is on, press the START/STOP button to turn it off.
(2)  Press the “ 

 ” button and “

” button at the same time for 

more than 2 seconds to start the test operation.

 

The operation lamp will light up and “ 

 ” will be displayed on the set 

temperature display.

*  Perform the test operation for 60 minutes.

*  Pressing the START/STOP button will stop the test operation.

Test operation display

9373328162-04_IM.indb   Sec1:7

9373328162-04_IM.indb   Sec1:7

2011-12-5   14:29:34

2011-12-5   14:29:34

Summary of Contents for UTY-RNN*M series

Page 1: ...our le personnel agréé uniquement MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала INSTALLATIONSANLEITUNG Nur für autorisiertes Personal MANUAL DE INSTALACIÓN Solo para personal autorizado MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MONTAJ KILAVUZU Yetkili...

Page 2: ...m being air conditioned will be sensed Do not locate directly exposed to the outlet air from the air conditioner Locate out of direct sunlight Locate away from the influence of other heat sources Do not touch the remote controller PC board and PC board parts directly with your hands Do not wire the remote controller cable and the bus wire together with or parallel to the connection cables transmis...

Page 3: ...ensor Button 14 Maintenance Filter Reset Button 15 Operation Lamp 16 Day Display 17 Operation Lock Display 18 Temperature Display 19 Fan Speed Display 20 Timer Mode Display 21 Operation Mode Display 22 Timer and Clock Display 23 Filter Display 24 Economy Display 25 Thermo Sensor Display 26 Vertical Swing Display 27 Horizontal Swing Display 28 Defrost Display 4 SELECTING AN INSTALLATION LOCATION 4 ...

Page 4: ... memory will be deleted if there is a power failure Factory setting 5 INSTALLING THE REMOTE CONTROLLER 5 1 Installation 5 1 1 INSTALLING THE REMOTE CONTROLLER Open the operation panel on the front of the remote controller remove the 2 screws indicated in the following figure and then remove the front case of the remote controller When installing the remote controller remove the connector from the ...

Page 5: ...roller cable 20 mm 5 3 2 WHEN CONNECTING TO THE EXCLUSIVE TERMINAL BLOCK Connect the end of remote controller cable directly to the exclusive terminal block Terminal block M4 screw 3 2 1 Earth Ground the remote controller if it has an earth a ground wire Black White Red Indoor unit side PCB Indoor unit Outdoor unit power supply terminal block Remote controller terminal block Remote controller cabl...

Page 6: ...re value between the temperature sensor of the indoor unit and the temperature sensor of the remote controller varies significantly it is likely to return to the control status of temperature sensor of the indoor unit temporarily As the temperature sensor of remote controller detects the temperature near the wall when there is a certain difference between the room temperature and the wall temperat...

Page 7: ...s in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting Description Function Number Setting Value Standard 11 00 Long interval 01 Short interval 02 No indication 03 The filter sign interval time is different according to Indoor unit type as follows Setting Description Compact Cassette Slim Duct Compact Wall Mounted Wall Mo...

Page 8: ...3 11 External input control Operation Stop mode or Forced stop mode can be elected Factory setting Setting Description Function Number Setting Value Operation Stop mode 46 00 Setting forbidden 01 Forced stop mode 02 12 Room temperature control switching Only for Wired remote controller This setting is used to set the room temperature control method when the wired remote controller is selected by t...

Page 9: ... Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7...

Page 10: ......

Reviews: