En-6

(5)  Press the TIMER SET button to con

fi

 rm the setting. 

Press the TIMER SET button for a few seconds until the setting value 
stops 

fl

 ashing.

If the setting value display changes or if “- -” is displayed when the 

fl

 ashing stops, the setting value has not been set correctly.

(An invalid setting value may have been selected for the indoor unit.)

Setting value

SU MO TU WE TH FR SA

                                                                                                                                               
(6)  Repeat steps 2 to 5 to perform additional settings. 

Press the “ 

 ” button, “ 

 ” button and 

” simultaneously again for more than 5 seconds to cancel the 

function setting mode. In addition, the function setting mode will be 
automatically canceled after 1 minute if no operation is performed.

                                                                                                                                               
(7)  After completing the FUNCTION SETTING, be sure to turn off the power 

and turn it on again.

Function Details

Functions

Function 

Number

Com-

pact 

Cas-

sette

Slim 

Duct

Com-

pact 
Wall 

Mounted

Wall 

Mounted

Floor

1) Filter sign

11

 *1

2) Ceiling height

20

3) Outlet directions

22

4)

Embedding 
the indoor unit 
in a wall

23

5) Static pressure

6)

Cooler room 
temperature 
correction

30

7)

Heater room 
temperature 
correction

31

8) Auto restart

40

9)

Indoor room 
temperature 
sensor switching 
function

42

10)

Remote control-
ler signal code

44

11)

External input 
control

46

12)

Room tem-
perature control 
switching

48

*1: It is effective only to install IR Receiver unit.

1) Filter sign

The indoor unit has a sign to inform the user that it is time to clean the 

fi

 lter. Select the time setting for the 

fi

 lter sign display interval in the table 

below according to the amount of dust or debris in the room. If you do 
not wish the 

fi

 lter sign to be displayed, select the setting value for “No 

indication”.

(

...  Factory setting)

Setting Description

Function Number

Setting Value

Standard

11

00

Long interval

01

Short interval

02

No indication

03

The 

fi

 lter sign interval time is different according to Indoor unit type as 

follows.

Setting Description 

Compact 
Cassette

Slim 

Duct

Compact Wall 

Mounted 

Wall 

Mounted

Floor

Standard

2,500 hours

400 hours

Long interval

4,400 hours

1,000 hours

Short interval

1,250 hours

200 hours

2) Ceiling height

Select the setting values in the table below according to the height of the 
ceiling.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

Standard (2.7m)

20

00

High ceiling (3.0m)

01

3) Outlet directions

Select the setting values in the table below for using a 3-way outlet.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

4-way

22

00

3-way

01

4) Embedding the indoor unit in a wall

When embedding the indoor unit in a wall, restrict the movement of the 
horizontal vane for the upper air outlet so that it only operates horizontally.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

Standard

23

00

(Setting forbidden)

01

In a wall

02

5) Static pressure

Select appropriate static pressure according to the installation conditions.
Please refer to the installation manual of each indoor unit for details. 

6) Cooler room temperature correction

Depending on the installed environment, the room temperature sensor 
may require a correction.  
The settings may be selected as shown in the table below.

(

...  Factory setting)

Setting Description 

Function Number

Setting Value

Standard

30

00

Slightly Lower control

01

Lower control

02

Warmer control

03

9373328162-04_IM.indb   Sec1:6

9373328162-04_IM.indb   Sec1:6

2011-12-5   14:29:33

2011-12-5   14:29:33

Summary of Contents for UTY-RNN*M series

Page 1: ...our le personnel agréé uniquement MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала INSTALLATIONSANLEITUNG Nur für autorisiertes Personal MANUAL DE INSTALACIÓN Solo para personal autorizado MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MONTAJ KILAVUZU Yetkili...

Page 2: ...m being air conditioned will be sensed Do not locate directly exposed to the outlet air from the air conditioner Locate out of direct sunlight Locate away from the influence of other heat sources Do not touch the remote controller PC board and PC board parts directly with your hands Do not wire the remote controller cable and the bus wire together with or parallel to the connection cables transmis...

Page 3: ...ensor Button 14 Maintenance Filter Reset Button 15 Operation Lamp 16 Day Display 17 Operation Lock Display 18 Temperature Display 19 Fan Speed Display 20 Timer Mode Display 21 Operation Mode Display 22 Timer and Clock Display 23 Filter Display 24 Economy Display 25 Thermo Sensor Display 26 Vertical Swing Display 27 Horizontal Swing Display 28 Defrost Display 4 SELECTING AN INSTALLATION LOCATION 4 ...

Page 4: ... memory will be deleted if there is a power failure Factory setting 5 INSTALLING THE REMOTE CONTROLLER 5 1 Installation 5 1 1 INSTALLING THE REMOTE CONTROLLER Open the operation panel on the front of the remote controller remove the 2 screws indicated in the following figure and then remove the front case of the remote controller When installing the remote controller remove the connector from the ...

Page 5: ...roller cable 20 mm 5 3 2 WHEN CONNECTING TO THE EXCLUSIVE TERMINAL BLOCK Connect the end of remote controller cable directly to the exclusive terminal block Terminal block M4 screw 3 2 1 Earth Ground the remote controller if it has an earth a ground wire Black White Red Indoor unit side PCB Indoor unit Outdoor unit power supply terminal block Remote controller terminal block Remote controller cabl...

Page 6: ...re value between the temperature sensor of the indoor unit and the temperature sensor of the remote controller varies significantly it is likely to return to the control status of temperature sensor of the indoor unit temporarily As the temperature sensor of remote controller detects the temperature near the wall when there is a certain difference between the room temperature and the wall temperat...

Page 7: ...s in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting Description Function Number Setting Value Standard 11 00 Long interval 01 Short interval 02 No indication 03 The filter sign interval time is different according to Indoor unit type as follows Setting Description Compact Cassette Slim Duct Compact Wall Mounted Wall Mo...

Page 8: ...3 11 External input control Operation Stop mode or Forced stop mode can be elected Factory setting Setting Description Function Number Setting Value Operation Stop mode 46 00 Setting forbidden 01 Forced stop mode 02 12 Room temperature control switching Only for Wired remote controller This setting is used to set the room temperature control method when the wired remote controller is selected by t...

Page 9: ... Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7...

Page 10: ......

Reviews: