5.3. Connection of Remote Controller Cable

CAUTION

When connecting the remote controller cable to the wall mounted type 

• 

and the 

fl

 oor type indoor unit, do not connect it to the outdoor unit or 

the indoor unit power terminal block. It may cause a failure.

There are 2 methods to connect the remote controller cable to the indoor 
unit. One is the connection using contained connecting cable and the other 
is the connection the remote controller cable is connected to the exclusive 
terminal block of the indoor unit.
Exclusive terminal block for remote controller connection method is different 
depending on each model. Modify the remote controller cable as per below 
description and connect it.
(For the details, refer to the installation manual of the indoor unit to be used.)

5.3.1.  WHEN CONNECTING TO THE WALL 

MOUNTED TYPE AND THE FLOOR TYPE 
CONNECTOR

Connect the remote controller cable to the connecting cable and insert it to 
the connector.

Pattern 1

PCB

Connecting cable

Remote controller 
cable

Indoor unit

Outdoor 
unit / 
power 
supply 
terminal 
block

Connector

Pattern 2

PCB

Connecting cable

Remote controller 
cable

Indoor unit

Outdoor 
unit / 
power 
supply 
terminal 
block

Connector

Communication 

kit (option)

Modify the cable as per below methods.
(1)  Use a tool to cut off the terminal on the end of the remote controller cable 

and then remove the insulation from the cut end of the cable as shown 
in Fig. 1.

(2)  Connect the remote controller cable and connecting cable as shown in   

Fig. 2.

(3) Be sure to insulate the connection between the cables.

Connecting 
cable

Connector

Fig. 1

Fig. 2

White

Red

White

Red

Black

Black

Insulated
connection

Remote
controller cable

Remote
controller cable

20 mm 

5.3.2.  WHEN CONNECTING TO THE EXCLUSIVE 

TERMINAL BLOCK

Connect the end of remote controller cable directly to the exclusive terminal 
block.

Terminal block

M4 screw

3
2
1

*

* Earth (Ground) the remote 
   controller if it has an earth 
  (a ground) wire.

Black
White
Red

Indoor unit 
side

PCB

Indoor unit

Outdoor unit /
power supply
terminal block

Remote controller
terminal block

Remote controller 
cable

  It may be failed if it is connected to the outdoor unit or the terminal block 

for power supply.

d

6. INSTALLATION METHODS

6.1. Group control

A number of indoor units can be operated at the same time using a single 

• 

remote controller.
Depending on the model, some indoor units cannot be connected for 

• 

group control. (Group control is available for the duct type, the cassette 
type and the ceiling type indoor unit.)
Some functions may become unusable, depending on the combination of 

• 

the indoor units that are connected in a group.

(1) Wiring method (indoor unit to remote controller)

EXAMPLE: Single Type

Remote controller

Remote controller
cable

Indoor unit 0

Indoor unit 1

Indoor unit 2

Indoor unit 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

When there is an earth (a ground) cable.

(2) Indoor unit address setting

Set each indoor unit address using the DIP switch of each indoor unit. 
(Refer to the installation manual for the indoor unit.)

6.2.  Dual remote controllers

Depending on the model, some indoor units cannot be connected for dual 

• 

remote controllers. (Dual remote controllers are available for the duct 
type, the cassette type and the ceiling type indoor unit.)
Two separate remote controllers can be used to operate the indoor units.

• 

The timer and self-diagnosis functions cannot be used on the slave units.

• 
(1) Wiring method (indoor unit to remote controller)

Remote controller cable

Indoor unit

Slave unit

Master unit

1 2 3

1 2 3

1 2 3

Remote controller

When there are 
earth (ground) 
cables.

9373328162-04_IM.indb   Sec1:4

9373328162-04_IM.indb   Sec1:4

2011-12-5   14:29:30

2011-12-5   14:29:30

Summary of Contents for UTY-RNN*M series

Page 1: ...our le personnel agréé uniquement MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала INSTALLATIONSANLEITUNG Nur für autorisiertes Personal MANUAL DE INSTALACIÓN Solo para personal autorizado MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MONTAJ KILAVUZU Yetkili...

Page 2: ...m being air conditioned will be sensed Do not locate directly exposed to the outlet air from the air conditioner Locate out of direct sunlight Locate away from the influence of other heat sources Do not touch the remote controller PC board and PC board parts directly with your hands Do not wire the remote controller cable and the bus wire together with or parallel to the connection cables transmis...

Page 3: ...ensor Button 14 Maintenance Filter Reset Button 15 Operation Lamp 16 Day Display 17 Operation Lock Display 18 Temperature Display 19 Fan Speed Display 20 Timer Mode Display 21 Operation Mode Display 22 Timer and Clock Display 23 Filter Display 24 Economy Display 25 Thermo Sensor Display 26 Vertical Swing Display 27 Horizontal Swing Display 28 Defrost Display 4 SELECTING AN INSTALLATION LOCATION 4 ...

Page 4: ... memory will be deleted if there is a power failure Factory setting 5 INSTALLING THE REMOTE CONTROLLER 5 1 Installation 5 1 1 INSTALLING THE REMOTE CONTROLLER Open the operation panel on the front of the remote controller remove the 2 screws indicated in the following figure and then remove the front case of the remote controller When installing the remote controller remove the connector from the ...

Page 5: ...roller cable 20 mm 5 3 2 WHEN CONNECTING TO THE EXCLUSIVE TERMINAL BLOCK Connect the end of remote controller cable directly to the exclusive terminal block Terminal block M4 screw 3 2 1 Earth Ground the remote controller if it has an earth a ground wire Black White Red Indoor unit side PCB Indoor unit Outdoor unit power supply terminal block Remote controller terminal block Remote controller cabl...

Page 6: ...re value between the temperature sensor of the indoor unit and the temperature sensor of the remote controller varies significantly it is likely to return to the control status of temperature sensor of the indoor unit temporarily As the temperature sensor of remote controller detects the temperature near the wall when there is a certain difference between the room temperature and the wall temperat...

Page 7: ...s in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting Description Function Number Setting Value Standard 11 00 Long interval 01 Short interval 02 No indication 03 The filter sign interval time is different according to Indoor unit type as follows Setting Description Compact Cassette Slim Duct Compact Wall Mounted Wall Mo...

Page 8: ...3 11 External input control Operation Stop mode or Forced stop mode can be elected Factory setting Setting Description Function Number Setting Value Operation Stop mode 46 00 Setting forbidden 01 Forced stop mode 02 12 Room temperature control switching Only for Wired remote controller This setting is used to set the room temperature control method when the wired remote controller is selected by t...

Page 9: ... Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7...