U41644-J-Z816-5-76
2-11
Laufende K/F 1
2.2.3
Notes on cabling PRIMEQUEST 520A*/520/420
When determining the total length of the cable to be connected to the PRIMEQUEST
520A*/520/420, allow for an extra length of cable for pulling out the units.
PRIMEQUEST 520A*/520/420 needs to be pulled out from the rack for maintenance.
The cable is routed with the cable-management system. For the cable-management
system, extra cable length of 2 m (6.6 ft.) is required.
Use a sheathless optical cable for the fibre channel cable. (If the sheath fibre
channel cable has been laid, connect a sheathless optical Fibre Channel cable
with an adapter (DCBL-FCE02 (SC-LC: 2m (6.6 ft.)), DCBL-FCE05 (SC-LC: 5m
(16.4 ft.)), DCBL-FCG02 (LC-LC: 2m (6.6 ft.)) or DCBL-FCG05 (LC-LC: 5m
(16.4 ft.))) to the sheath fibre channel cable.)
Avoid laying the power cable close to metal cables such as RS232C or SCSI
cables. If cables need to be crossed, avoid laying the sheathless optical cable
under power cables or metal cables.
*: not supported by Fujitsu Technology Solutions