C141-E134-01EN
4 - 6
(4)
Environmental temperature
Temperature condition at installed in a cabinet is indicated with ambient temperature measured 3
cm from the disk drive. At designing the system cabinet, consider following points.
•
Make a suitable air flow so that the DE surface temperature does not exceed 55°C.
•
Cool the PCA side especially with air circulation inside the cabinet. Confirm the cooling effect
by measuring temperature of specific ICs and the DE. These measurement results should be
within a criteria listed in Table 4.1.
Table 4.1
Surface temperature check point
No.
Measurement point
Criteria
1
Center of DE cover
55°C
2
Read channel LSI
90°C
3
VCM/SPM Driver
92°C
4
HDC
89°C
5
MPU
88°C
1
4
5
2
3
Figure 4.6 Surface temperature measurement points
(5)
Service clearance area
The service clearance area, or the sides which must allow access to the IDD for installation or
maintenance, is shown in Figures 4.7.
Summary of Contents for MAM3184MC
Page 1: ...C141 E134 01EN MAM3367MC MP SERIES MAM3184MC MP SERIES DISK DRIVES PRODUCT MAINTENANCE MANUAL ...
Page 18: ...This page is intentionally left blank ...
Page 28: ...This page is intentionally left blank ...
Page 36: ...This page is intentionally left blank ...
Page 66: ...C141 E134 01EN 4 14 Figure 4 17 External operator panel connector CN2 ...
Page 124: ...8 8 C141 E134 01EN Figure 8 3 Block diagram of read write circuit ...
Page 130: ...This page is intentionally left blank ...
Page 134: ...This page is intentionally left blank ...
Page 140: ...This page is intentionally left blank ...
Page 148: ...This page is intentionally left blank ...
Page 150: ...This page is intentionally left blank ...
Page 151: ......
Page 152: ......